NEC Power-Limited Wiring Requirements for eFlow3N Models:

Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit 

wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited 

circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. 

One such example of this is shown below. Your specific application may require different conduit knockouts to 

be used. Any conduit knockouts may be used. For power- limited applications use of conduit is optional. All field 

wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute).

Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods.

For Canadian installations use shielded wiring for all connections.

Note:

 Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire 

(Fig. 5a).

Fig. 5

Fig. 5a

 Input 120VAC 60Hz

(non power-limited)

Optional UL Listed 

Battery Enclosure

(non power-limited)

Supervisory,

Fire Alarm

Interface and

Aux. output

Connections

(power-limited)

External

Jacketed

Shield

Incorrect Wire

Handling

Correct Wire

Handling

Pull back

external jacketed

shield approx. 1/2”.

Wire

Insulation

Solid Copper

Conductors

DC Outputs

(power-limited)

Power 

Distribution

(power-

limited)

Battery Connections

(non power-limited)

Summary of Contents for eFlow3N

Page 1: ...4 2A 12VDC or 24VDC Four 4 Class 2 Power Limited Fused Outputs eFlow3N4D eFlow3NX4D 2A 12VDC or 24VDC Four 4 Class 2 Power Limited PTC Outputs Installation Guide Rev 3NRP013019 More than just power TM...

Page 2: ...4 2A P eFlow3NX4D 2A P These units are classified as Power Limited stand alone power supplies with stand by battery and they are suitable to power sensors electro mechanical devices e g electric door...

Page 3: ...fer to Appendix A pg 13 4 Measure output voltage before connecting devices This helps avoiding potential damage 5 Connect devices to be powered a For eFlow3N eFlow3NX connect devices to terminals mark...

Page 4: ...or Access Control Applications mount UL Listed tamper switch Altronix Model TS112 or equivalent at the top of the enclosure Slide tamper switch bracket onto the edge or the enclosure approx 2 from the...

Page 5: ...is present Contact rating 1A 30VDC A removed battery is reported within 5 minutes Battery reconnection is reported within 1 minute power limited Fig 1b pg 5 BAT Stand by battery connections Maximum ch...

Page 6: ...inals marked BAT FAIL C NO Fig 2 pg 6 NC C NO NC C NO BAT FAIL AC FAIL POWER SOURCE RED INDICATING LAMP Power Distribution Module s Fig 3a PD4UL Power Distribution Board Fig 3b PD4ULCB Power Distribut...

Page 7: ...e required for UL603 UL1481 and Canadian installations Optional Rechargeable Stand by Battery for UL294 Applications Note 12V batteries are required for UL603 UL1481 and Canadian installations CAUTION...

Page 8: ...nal All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power suppl...

Page 9: ...ble Stand by Battery for UL294 Applications Note 12V batteries required for ULC S319 installations CAUTION When power supply board is set for 12VDC use only one 1 12VDC stand by battery Keep power lim...

Page 10: ...ional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power sup...

Page 11: ...6mm 1 40 35 6mm 1 40 35 6mm 4 85 123 2mm 4 85 123 2mm 3 25 82 6mm 0 75 19 1mm 0 75 19 1mm 11 0 279 4mm 12 5 317 5mm 1 20 30 5mm 1 20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1 40 35 6mm 5 10 1...

Page 12: ...1 375 34 9mm 1 125 28 6mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 4 5 114 3mm 4 5 114 3mm 1 25 31 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9m...

Page 13: ...24TB Photoelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 39 2W MOD Loop Test Maintenance Mod 30 50...

Page 14: ...mote control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output...

Page 15: ...ltronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warra...

Page 16: ...2A Over 4 Hours 2A Battery Backup Built in charger for sealed lead acid or gel type batteries Maximum charge current 1 54A Automatic switch over to stand by battery when AC fails Transfer to stand by...

Reviews: