Overview:

Altronix eFlowNA8V Series units distribute and switch power to access control systems and accessories. They 
convert a 220VAC (working range 198VAC - 256VAC), 50/60Hz input into eight (8) independently controlled 
12VDC or 24VDC fuse protected outputs. These power outputs can be converted to dry form “C” contacts. 
Outputs are activated by an open collector sink or normally open (NO) dry trigger input from an Access Control 
System, Card Reader, Keypad, Push Button, PIR, etc. Units will route power to a variety of access control hard-
ware devices including: Mag Locks, Electric Strikes, Magnetic Door Holders, etc. Outputs will operate in both 
Fail-Safe and/or Fail-Secure modes. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may 
be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or 
all of the eight (8) outputs.

eFlowNA8V Series Configuration Reference Chart:

Altronix
Model 
Number

Nominal DC Output 

Voltage Options

Maximum Supply

Current for

Main and Aux. 

Outputs (A)

Fuse Protected Outputs

220VAC 50/60 Hz

Input (current)

Current per ACM8

output (A)

Power Supply Board

Input Fuse Rating

Power Supply Board

Battery Fuse Rating

ACM8 Board

Input Fuse Rating

ACM8 Board

Output Fuse Rating

[DC]

[AUX]

12VDC Output

Range (V)

24VDC Output

Range (V)

12VDC Output

Range (V)

24VDC Output

Range (V) 12VDC 24VDC

eFlow4NA8V

10.1-

13.2

20.28-

26.4

10.05-

13.2

20.2-

26.4

3.3A

3.6A

8

2.1A 2.5A

5A/

250V

7.5A/

32V

10A/

250V

3.5A/
250V

eFlow6NA8V

10.0-

13.2

20.19-

26.4

10.03-

13.2

20.19-

26.4

5.3A

5.6A

8

2.1A 2.5A

5A/

250V

10A/

32V

10A/

250V

3.5A/
250V

eFlow102NA8V

10.03-

13.2

10.03-

13.2

9.3A

8

2.1A 2.5A

5A/

250V

15A/

32V

10A/

250V

3.5A/
250V

eFlow104NA8V

20.17-

26.4

20.17-

26.4

9.6A

8

2.7A 2.5A

6.3A/
250V

15A/

32V

10A/

250V

3.5A/
250V

*eFlow4NA8V only: This unit is classified as power-limited stand alone power supply with stand-by battery 
and it is suitable to power: sensors, electro-mechanical devices (e.g. electric door strikes).

*eFlow6NA8V, eFlow102NA8V, and eFlow104NA8V: The DC output for these power supplies are not power-
limited. If a power-limited output is required in the end-product application, the DC output from the power supply 
must be connected to a separately Listed control unit or accessory board that provides power-limited outputs. 
The product(s) providing the power-limited output(s) must be listed as appropriate for the particular end-product 
application (access control), and wired in accordance with the products installation instructions. Class 1 wiring 
methods, separation of circuits, and proper fire-rated enclosures all must be considered when connecting the DC 
output of the power supply to the end-product devices. The auxiliary outputs of these units are power-limited.

Specifications:

ACM8 Access Power Controller Module:

•  Eight (8) independently trigger controlled outputs. Output options:
  a) Eight (8) Fail-Safe filtered power outputs.
  b) Eight (8) Fail-Secure filtered power outputs.
  c) Eight (8) form “C” relay outputs (rated @ 5A/24VDC or VAC).
  d) Any combination of the above. 
•  Eight (8) Access Control System trigger inputs. Input trigger options:
  a) Eight (8) normally open (NO) dry trigger inputs.
  b) Eight (8) open collector inputs.
  c) Any combination of the above.
•  Eight (8) unswitched filtered aux. power outputs (outputs are rated @ 2.5A).
•  Red LEDs on ACM8 board indicate individual outputs are triggered (relays energized).
•  Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the eight (8) outputs.
  Fire Alarm disconnect input trigger options:
  a) Normally open (NO) or normally closed (NC) dry trigger input.
  b) Polarity reversal input from FACP signaling circuit.
•  Green LED on ACM8 board indicates FACP disconnect is triggered.
•  FACP output relay indicates that FACP input is triggered (form “C” contact rated @ 1A/28VDC).
•  eFlow Power Supply/Charger provides common power for ACM8 board and all connected 
  access control devices.
•  ACM8 board main fuses are rated @ 10A. Output fuses are rated @ 3.5A.

Summary of Contents for eFlow102NA8V

Page 1: ...eFlow102NA8V eFlow104NA8V 10A 12VDC 10A 24VDC Eight 8 Fused Outputs Eight 8 Fused Outputs For a red enclosure add an R suffix to the part e g eFlow4NA8VR Rev eFlowNA8V062717 More than just power TM In...

Page 2: ...y Battery Specifications pg 8 Power Supply Board Output Voltage Settings pg 8 Access Power Controller Typical Application Diagram ACM8 pg 8 NEC Power Limited Wiring Requirements for eFlowNA8V Models p...

Page 3: ...battery and it is suitable to power sensors electro mechanical devices e g electric door strikes eFlow6NA8V eFlow102NA8V and eFlow104NA8V The DC output for these power supplies are not power limited...

Page 4: ...rews Install the two lower screws and make sure to tighten all screws Enclosure Dimensions pg 16 2 Connect AC circuit 220VAC 50 60Hz as follows Green branch wire connects to earth safety ground Line a...

Page 5: ...CP for normally closed output 10 Stand by Battery Connections Fig 3 pg 9 For U S Access Control applications batteries are optional Batteries are required for Canadian installations ULC S319 When batt...

Page 6: ...terminal marked INP to reset FACP Signal Circuit Input It is necessary to trigger the Fire Alarm System In all of the above scenarios the green TRG LED of the ACM8 will illuminate All outputs selected...

Page 7: ...l Identification Terminal Legend Function Description Power 12VDC or 24VDC from power supply charger factory connected These terminals are paralleled to the Control terminals Control These terminals a...

Page 8: ...romagnetic Door Holders AC or DC Power Supply optional AC or DC Power Supply req d FACP Fire Alarm Control Panel UL Listed Power Supply For this application corresponding fuse F8 must be removed Keypa...

Page 9: ...ted for all other models Fire Alarm Interface power limited Inputs power limited J2 F8 J1 J3 1 2 3 4 O N 1 2 3 4 O N Ground Lug Unswitched 220VAC power mains Non power limited Battery Connections non...

Page 10: ...ections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring meth...

Page 11: ...ig 5 Optional hook up using two 2 isolated power supply inputs Only applicable on eFlow4NA8V Fig 6 Polarity reversal input from FACP signaling circuit output polarity is referenced in alarm condition...

Page 12: ...r input with reset Fig 9 Normally Closed Non Latching FACP trigger input Fig 10 Normally Closed Latching FACP trigger input with reset N C RESET SWITCH N O TRIGGER INPUT JUMPER TRG NO C NC JUMPER N C...

Page 13: ...rol of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output state cha...

Page 14: ...14 eFlowNA8V Series Notes...