- 4 - 

eFlowNA8V Series

eFlowV Power Supply/Charger:

•  Input: 220VAC (working range 198VAC - 256VAC), 50/60Hz. 
•  For output voltage and supply current refer to eFlowNA8V Series Configuration Chart, pg. 3.
•  Auxiliary power-limited output rated @ 1A (unswitched).
•  Overvoltage protection.
•  Built-in charger for sealed lead acid or gel type batteries.
•  Maximum charge current 1.54A.
•  Automatic switch over to stand-by battery when AC fails. 
  Transfer to stand-by battery power is instantaneous with no interruption.
•  Supervised Fire Alarm disconnect (latching or non-latching) 10K EOL resistor. 
  Operates on a normally open (NO) or normally closed (NC) trigger.
•  AC fail supervision (form “C” contacts).
•  Battery fail and presence supervision (form “C” contacts).
•  Low power shutdown. Shuts down DC output terminals if battery voltage drops below 71-73% for 12V units 
  and 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge.
•  For fuse rating, refer to eFlowNA8V series Configuration Chart, pg. 3.
•  Green AC Power LED indicates 120VAC present.
•  AC input and DC output LED indicators.
•  Short circuit and overload protection.
•  Enclosure accommodates up to two (2) 12AH batteries.
Enclosure dimensions: 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm).

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, The Canadian Electri-
cal Code, Part I, Part II and with all local codes and authorities having jurisdiction. The product must be located 
indoors within the protected premises. 
 

Power Supply Board LED Diagnostics 

(pg. 6)

 

Access Power Controller LED Diagnostics 

(pg. 6)

 

Power Supply Board Terminal Identification 

(pg. 7)

 

Access Power Controller Terminal Identification 

(pg. 7)

 

Power Supply Board Stand-by Battery Specifications 

(pg. 8)

 

Power Supply Board Output Voltage Settings 

(pg. 8)

 

Access Power Controller Typical Application Diagram 

(pg. 8)

 

FACP/Optional Power Supply Hook-up Diagrams 

(pg. 11-12)

1.  Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in 
 

the  enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place 

 

the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower 

 

two holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s 

 

upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws. 

 

Enclosure Dimensions, pg. 16.

2.  Connect AC circuit (220VAC, 50/60Hz) as follows: Green branch wire connects to earth (safety) 
 

ground    . Line and Neutral to the connector on power supply board marked [L, N] respectively 

 

(Fig. 3, pg. 9). Do not use terminal marked [G]. Use 14 AWG or larger for all power connections. 

 

Secure green wire lead attached to the chassis to earth ground.

 

Keep power-limited wiring separate from non power-limited wiring. 

 

Minimum 0.25” spacing must be provided (Fig. 3, pg. 9).

 

CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or 

 

servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to 

 

qualified service personnel.

3.  Select desired DC output voltage by setting SW1 to the appropriate position on the power supply board 
 

(eFlow4NA8V and eFlow6NA8V) (Fig. 1, pg. 8). eFlow102NA8V power supply is factory set at 12VDC. 

 

eFlow104NA8V power supply is factory set at 24VDC.

4.  Measure the output voltage of the unit before connecting any devices to ensure proper operation.
 

Improper or high voltage will damage these devices.

5. 

Output options (Fig. 2, pg. 8):

 

The unit will provide either eight (8) switched power outputs, eight (8) dry form “C” outputs, or any

 

combination of both switched power and form “C” outputs.

 

(a)  Fail-Safe Switched Power outputs: 

 

 

For Fail-Safe operation connect the positive (+) input of the access control devices to terminal marked 

 

 

[NC]. Connect the negative (–) input of the access control devices to terminal marked [COM].

 

(b) Fail-Secure Switched Power outputs:

 

 

For Fail-Secure operation connect the positive (+) input of the access control devices to terminal 

 

 

marked [NO]. Connect the negative (–) input of the access control devices to terminal marked [COM].

NC  C  NO  NC  C  NO

AC FAIL

BAT FAIL

TRIGGER

AC DC

AC1

EOL NO GND

SUPERVISED

RESET

+AUX-

-    BAT    

+

-    DC    

+

L      G      N

1 min   enable
2 hr      disable

OFF - 24

V

ON - 12V

ON

power-limited

NC  C  NO COM

OUTPUT 3

NC  C  NO COM NC  C  NO COM

OUTPUT 2

LED2

OUTPUT 1

LED1

LED3

NC  C  NO COM

OUTPUT 5

LED6

NC  C  NO COM

OUTPUT 4

LED4

LED5

NC  C  NO COM

OUTPUT 6

LED7

NC  C  NO COM

OUTPUT 7

LED8

IN  GND

1

IN  GND IN  GND

2

IN  GND

5

IN  GND

IN  GND

3

4

IN  GND

6

7

IN  GND

8

+

-
+

-

NC  C  NO COM

OUTPUT 8

POWE

RC

ONTROL

-

-

+

IM

P

+
T

RE

T

NO   C    NC

TRG

FACP

INTERF

ACE

DC Output to devices (power-limited for eFlow4NA8V, 

non power-limited for all other models*)

Fire Alarm Interface

(power-limited)

Inputs (power-limited)

J2

F8

J1

J3

1     2     3     4

O N

1     2     3     4

O N

Ground Lug

Unswitched 220VAC 

power mains

Non power-limited

Battery Connections

(non power-limited)

CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery.

Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.

12AH Rechargeable batteries are the largest batteries that can fit in this enclosure.

A UL listed external battery enclosure must be used if using the 40AH or 65AH batteries.

Optional Rechargeable

Stand-by Battery

Optional Rechargeable

Stand-by Battery

Tamper Switch

Summary of Contents for eFlow102NA8V

Page 1: ...eFlow102NA8V eFlow104NA8V 10A 12VDC 10A 24VDC Eight 8 Fused Outputs Eight 8 Fused Outputs For a red enclosure add an R suffix to the part e g eFlow4NA8VR Rev eFlowNA8V062717 More than just power TM In...

Page 2: ...y Battery Specifications pg 8 Power Supply Board Output Voltage Settings pg 8 Access Power Controller Typical Application Diagram ACM8 pg 8 NEC Power Limited Wiring Requirements for eFlowNA8V Models p...

Page 3: ...battery and it is suitable to power sensors electro mechanical devices e g electric door strikes eFlow6NA8V eFlow102NA8V and eFlow104NA8V The DC output for these power supplies are not power limited...

Page 4: ...rews Install the two lower screws and make sure to tighten all screws Enclosure Dimensions pg 16 2 Connect AC circuit 220VAC 50 60Hz as follows Green branch wire connects to earth safety ground Line a...

Page 5: ...CP for normally closed output 10 Stand by Battery Connections Fig 3 pg 9 For U S Access Control applications batteries are optional Batteries are required for Canadian installations ULC S319 When batt...

Page 6: ...terminal marked INP to reset FACP Signal Circuit Input It is necessary to trigger the Fire Alarm System In all of the above scenarios the green TRG LED of the ACM8 will illuminate All outputs selected...

Page 7: ...l Identification Terminal Legend Function Description Power 12VDC or 24VDC from power supply charger factory connected These terminals are paralleled to the Control terminals Control These terminals a...

Page 8: ...romagnetic Door Holders AC or DC Power Supply optional AC or DC Power Supply req d FACP Fire Alarm Control Panel UL Listed Power Supply For this application corresponding fuse F8 must be removed Keypa...

Page 9: ...ted for all other models Fire Alarm Interface power limited Inputs power limited J2 F8 J1 J3 1 2 3 4 O N 1 2 3 4 O N Ground Lug Unswitched 220VAC power mains Non power limited Battery Connections non...

Page 10: ...ections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring meth...

Page 11: ...ig 5 Optional hook up using two 2 isolated power supply inputs Only applicable on eFlow4NA8V Fig 6 Polarity reversal input from FACP signaling circuit output polarity is referenced in alarm condition...

Page 12: ...r input with reset Fig 9 Normally Closed Non Latching FACP trigger input Fig 10 Normally Closed Latching FACP trigger input with reset N C RESET SWITCH N O TRIGGER INPUT JUMPER TRG NO C NC JUMPER N C...

Page 13: ...rol of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output state cha...

Page 14: ...14 eFlowNA8V Series Notes...

Page 15: ...eFlowNA8V Series 15 Notes...

Page 16: ...38 1mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 1 5 38 1mm 2 0 50 8mm 2 0 50 8mm 1 75 44 45mm 1 75 44 45mm 4 5 114 3mm 1 25 31 75mm 4 5 114 3mm 1 25 31 75mm 1 25 31 75mm 1 25 31 75mm 1 1 27 94mm...

Reviews: