- 4 -
eFlowNA8V Series
eFlowV Power Supply/Charger:
• Input: 220VAC (working range 198VAC - 256VAC), 50/60Hz.
• For output voltage and supply current refer to eFlowNA8V Series Configuration Chart, pg. 3.
• Auxiliary power-limited output rated @ 1A (unswitched).
• Overvoltage protection.
• Built-in charger for sealed lead acid or gel type batteries.
• Maximum charge current 1.54A.
• Automatic switch over to stand-by battery when AC fails.
Transfer to stand-by battery power is instantaneous with no interruption.
• Supervised Fire Alarm disconnect (latching or non-latching) 10K EOL resistor.
Operates on a normally open (NO) or normally closed (NC) trigger.
• AC fail supervision (form “C” contacts).
• Battery fail and presence supervision (form “C” contacts).
• Low power shutdown. Shuts down DC output terminals if battery voltage drops below 71-73% for 12V units
and 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge.
• For fuse rating, refer to eFlowNA8V series Configuration Chart, pg. 3.
• Green AC Power LED indicates 120VAC present.
• AC input and DC output LED indicators.
• Short circuit and overload protection.
• Enclosure accommodates up to two (2) 12AH batteries.
Enclosure dimensions: 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm).
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, The Canadian Electri-
cal Code, Part I, Part II and with all local codes and authorities having jurisdiction. The product must be located
indoors within the protected premises.
Power Supply Board LED Diagnostics
(pg. 6)
Access Power Controller LED Diagnostics
(pg. 6)
Power Supply Board Terminal Identification
(pg. 7)
Access Power Controller Terminal Identification
(pg. 7)
Power Supply Board Stand-by Battery Specifications
(pg. 8)
Power Supply Board Output Voltage Settings
(pg. 8)
Access Power Controller Typical Application Diagram
(pg. 8)
FACP/Optional Power Supply Hook-up Diagrams
(pg. 11-12)
1. Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in
the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place
the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower
two holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s
upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws.
Enclosure Dimensions, pg. 16.
2. Connect AC circuit (220VAC, 50/60Hz) as follows: Green branch wire connects to earth (safety)
ground . Line and Neutral to the connector on power supply board marked [L, N] respectively
(Fig. 3, pg. 9). Do not use terminal marked [G]. Use 14 AWG or larger for all power connections.
Secure green wire lead attached to the chassis to earth ground.
Keep power-limited wiring separate from non power-limited wiring.
Minimum 0.25” spacing must be provided (Fig. 3, pg. 9).
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or
servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to
qualified service personnel.
3. Select desired DC output voltage by setting SW1 to the appropriate position on the power supply board
(eFlow4NA8V and eFlow6NA8V) (Fig. 1, pg. 8). eFlow102NA8V power supply is factory set at 12VDC.
eFlow104NA8V power supply is factory set at 24VDC.
4. Measure the output voltage of the unit before connecting any devices to ensure proper operation.
Improper or high voltage will damage these devices.
5.
Output options (Fig. 2, pg. 8):
The unit will provide either eight (8) switched power outputs, eight (8) dry form “C” outputs, or any
combination of both switched power and form “C” outputs.
(a) Fail-Safe Switched Power outputs:
For Fail-Safe operation connect the positive (+) input of the access control devices to terminal marked
[NC]. Connect the negative (–) input of the access control devices to terminal marked [COM].
(b) Fail-Secure Switched Power outputs:
For Fail-Secure operation connect the positive (+) input of the access control devices to terminal
marked [NO]. Connect the negative (–) input of the access control devices to terminal marked [COM].
NC C NO NC C NO
AC FAIL
BAT FAIL
TRIGGER
AC DC
AC1
EOL NO GND
SUPERVISED
RESET
+AUX-
- BAT
+
- DC
+
L G N
1 min enable
2 hr disable
OFF - 24
V
ON - 12V
ON
power-limited
NC C NO COM
OUTPUT 3
NC C NO COM NC C NO COM
OUTPUT 2
LED2
OUTPUT 1
LED1
LED3
NC C NO COM
OUTPUT 5
LED6
NC C NO COM
OUTPUT 4
LED4
LED5
NC C NO COM
OUTPUT 6
LED7
NC C NO COM
OUTPUT 7
LED8
IN GND
1
IN GND IN GND
2
IN GND
5
IN GND
IN GND
3
4
IN GND
6
7
IN GND
8
+
-
+
-
NC C NO COM
OUTPUT 8
POWE
RC
ONTROL
-
-
+
IM
P
+
T
RE
T
NO C NC
TRG
FACP
INTERF
ACE
DC Output to devices (power-limited for eFlow4NA8V,
non power-limited for all other models*)
Fire Alarm Interface
(power-limited)
Inputs (power-limited)
J2
F8
J1
J3
1 2 3 4
O N
1 2 3 4
O N
Ground Lug
Unswitched 220VAC
power mains
Non power-limited
Battery Connections
(non power-limited)
CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
12AH Rechargeable batteries are the largest batteries that can fit in this enclosure.
A UL listed external battery enclosure must be used if using the 40AH or 65AH batteries.
Optional Rechargeable
Stand-by Battery
Optional Rechargeable
Stand-by Battery
Tamper Switch