NEC Power-Limited Wiring Requirements for eFlowNA8V Models:
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited
circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all
power-limitedcircuit wiring and non power-limited circuit wiring must enter and exit the cabinet through differ-
ent conduits. One such example of this is shown below. Your specific application may require different conduit
knockouts to be used. Any conduit knockouts may be used. For power- limited applications use of conduit is
optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or
equivalent substitute).
Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods.
For Canadian installations use shielded wiring for all connections.
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 4a).
Fig. 4
Input
220VAC
50/60Hz
(non power-
limited)
Supervisory Connections
(power-limited)
ACM8
outputs*
Battery
Connections
(non power-
limited)
Optional
UL Listed
Battery
Enclosure
(non power-
limited)
External
Jacketed
Shield
Incorrect Wire
Handling
Correct Wire
Handling
Pull back
external jacketed
shield approx. 1/2”.
Wire
Insulation
Solid Copper
Conductors
* Outputs are power-limited on eFlow4NA8V.
Outputs are non power-limited for eFlow6NA8V,
eFlow102NA8V, and eFlow104NA8V.
Fig. 4a
Summary of Contents for eFlow102NA8V
Page 14: ...14 eFlowNA8V Series Notes...
Page 15: ...eFlowNA8V Series 15 Notes...