NEC Power-Limited Wiring Requirements for eFlowNA8V Models:

Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited 
circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all 
power-limitedcircuit wiring and non power-limited circuit wiring must enter and exit the cabinet through differ-
ent conduits. One such example of this is shown below. Your specific application may require different conduit 
knockouts to be used. Any conduit knockouts may be used. For power- limited applications use of conduit is 
optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or 
equivalent substitute).
Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods.
For Canadian installations use shielded wiring for all connections.
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 4a).

Fig. 4

Input 

220VAC 

50/60Hz

(non power-

limited)

Supervisory Connections

(power-limited)

ACM8 

outputs*

Battery

Connections
(non power-

limited)

Optional

UL Listed

Battery 

Enclosure

(non power-

limited)

External

Jacketed

Shield

Incorrect Wire

Handling

Correct Wire

Handling

Pull back

external jacketed

shield approx. 1/2”.

Wire

Insulation

Solid Copper

Conductors

*  Outputs are power-limited on eFlow4NA8V.
  Outputs are non power-limited for eFlow6NA8V, 
  eFlow102NA8V, and eFlow104NA8V.

Fig. 4a

Summary of Contents for eFlow102NA8V

Page 1: ...eFlow102NA8V eFlow104NA8V 10A 12VDC 10A 24VDC Eight 8 Fused Outputs Eight 8 Fused Outputs For a red enclosure add an R suffix to the part e g eFlow4NA8VR Rev eFlowNA8V062717 More than just power TM In...

Page 2: ...y Battery Specifications pg 8 Power Supply Board Output Voltage Settings pg 8 Access Power Controller Typical Application Diagram ACM8 pg 8 NEC Power Limited Wiring Requirements for eFlowNA8V Models p...

Page 3: ...battery and it is suitable to power sensors electro mechanical devices e g electric door strikes eFlow6NA8V eFlow102NA8V and eFlow104NA8V The DC output for these power supplies are not power limited...

Page 4: ...rews Install the two lower screws and make sure to tighten all screws Enclosure Dimensions pg 16 2 Connect AC circuit 220VAC 50 60Hz as follows Green branch wire connects to earth safety ground Line a...

Page 5: ...CP for normally closed output 10 Stand by Battery Connections Fig 3 pg 9 For U S Access Control applications batteries are optional Batteries are required for Canadian installations ULC S319 When batt...

Page 6: ...terminal marked INP to reset FACP Signal Circuit Input It is necessary to trigger the Fire Alarm System In all of the above scenarios the green TRG LED of the ACM8 will illuminate All outputs selected...

Page 7: ...l Identification Terminal Legend Function Description Power 12VDC or 24VDC from power supply charger factory connected These terminals are paralleled to the Control terminals Control These terminals a...

Page 8: ...romagnetic Door Holders AC or DC Power Supply optional AC or DC Power Supply req d FACP Fire Alarm Control Panel UL Listed Power Supply For this application corresponding fuse F8 must be removed Keypa...

Page 9: ...ted for all other models Fire Alarm Interface power limited Inputs power limited J2 F8 J1 J3 1 2 3 4 O N 1 2 3 4 O N Ground Lug Unswitched 220VAC power mains Non power limited Battery Connections non...

Page 10: ...ections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring meth...

Page 11: ...ig 5 Optional hook up using two 2 isolated power supply inputs Only applicable on eFlow4NA8V Fig 6 Polarity reversal input from FACP signaling circuit output polarity is referenced in alarm condition...

Page 12: ...r input with reset Fig 9 Normally Closed Non Latching FACP trigger input Fig 10 Normally Closed Latching FACP trigger input with reset N C RESET SWITCH N O TRIGGER INPUT JUMPER TRG NO C NC JUMPER N C...

Page 13: ...rol of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output state cha...

Page 14: ...14 eFlowNA8V Series Notes...

Page 15: ...eFlowNA8V Series 15 Notes...

Page 16: ...38 1mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 1 5 38 1mm 2 0 50 8mm 2 0 50 8mm 1 75 44 45mm 1 75 44 45mm 4 5 114 3mm 1 25 31 75mm 4 5 114 3mm 1 25 31 75mm 1 25 31 75mm 1 25 31 75mm 1 1 27 94mm...

Reviews: