background image

 

AL1024NK1 Installation Guide 

- 3 -

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, The Canadian 

Electrical Code, Part 1 and with all local codes and authorities having jurisdiction. The product must be located 

indoors within the protected premises. 

1.  Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in 

 

the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the 

 

enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two 

 

holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s upper 

 

keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 

 

(Enclosure Dimensions, pg. 9)

. Secure enclosure to earth ground. 

2.  Connect unswitched AC power (115VAC, 60Hz) to terminals marked [L, N] 

(Fig. 1a, pg. 4)

. Use 14 AWG 

 

or larger for all power connections. Secure green wire lead to earth ground. 

 

Keep power-limited wiring separate from non power-limited wiring (115VAC 60Hz Input, 

 

Battery Wires). Minimum 0.25” spacing must be provided.

 

CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or 

 

servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to 

 

qualified service personnel.

3.  Measure output voltage before connecting devices. This helps avoiding potential damage.

4.  Select VR6’s output voltage (5VDC or 12VDC) using switch [S1] 

(Fig. 2a, pg. 5)

.

5.  Connect devices to be powered:

 

a.  For 24VDC connect device(s) to terminals marked [+ DC –] on AL1024ULXB2 (power supply board) 

   (

Fig. 1h, pg. 4, Fig. 2, pg. 5

). 

 

b.  For 5VDC or 12VDC connect device(s) to terminals marked [+ OUT –] on VR6

 (Fig. 2b, pg. 5)

 

 

Carefully observe correct polarity.

6.  For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result 

 

in the loss of the output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel 

 

type. Connect battery to terminals marked [– BAT +] 

(Fig. 1g, pg. 5)

. Use two (2) 12VDC batteries connected 

 

in series for 24VDC operation (battery leads included) Use batteries - Casil CL1270 (12V/7AH), 

 

CL12120 (12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or UL recognized BAZR2 

 

batteries of an appropriate rating.

7.  Connect appropriate signaling notification devices to AC FAIL & BAT FAIL 

(Fig. 1b, pg. 4)

 supervisory

 

relay outputs.

8.  To delay reporting for up to 6 hrs., cut “AC Delay” jumper and reset power to unit 

(Fig. 1f, pg. 4)

.

9.  For Access Control Applications: mount UL Listed tamper switch (Altronix model TS112 or equivalent) at 

 

the top of the enclosure. Slide tamper switch bracket onto the edge or the enclosure approx. 2” from the 

 

right side 

(Fig. 2, pg. 5)

. Connect tamper switch wiring to the Access Control Panel input or the appropriate 

 

UL Listed reporting device.

Wiring:

Use 18 AWG or larger for all low voltage power connections.

Note:

 Take care to keep power-limited circuits separate from non power-limited wiring (115VAC, Battery).

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test:

 Under normal load conditions, the DC output voltage should be checked for proper 

voltage level AL1024NK1: 24VDC nominal rated @ 10A max.

Battery Test:

 Under normal load conditions check that the battery is fully charged, check specified voltage

(24VDC @ 26.4) both at battery terminal and at the board terminals marked [– BAT +] to ensure that there is no 

break in the battery connection wires.

Note:

 Maximum charging current under discharges is 3.6A.

Note:

 Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.

Summary of Contents for AL1024NK1

Page 1: ...4ULXB2 Power Supply Charger 1 VR6 Voltage Regulator Installation Guide Rev 1024NK1_022322 More than just power TM Installing Company ________________ Service Rep Name _________________________________...

Page 2: ...00mA Alarm 10A For Access Control applications battery capacity for 10A supply current 1 hr for 24VDC 12AH battery 6 5 hrs for 24VDC 65AH battery See battery size calculation worksheet for other batte...

Page 3: ...terminals marked OUT on VR6 Fig 2b pg 5 Carefully observe correct polarity 6 For Access Control applications batteries are optional When batteries are not used a loss of AC will result in the loss of...

Page 4: ...esent Contact rating 1A 28VDC AC or brownout fail is reported within 1 minute of event To delay reporting for up to 6 hrs cut AC Delay jumper and reset power to unit Fig 1f pg 4 Bat Fail NC C NO Used...

Page 5: ...y board is factory set for 24VDC Use two 2 12VDC stand by batteries Keep power limited wiring separate from non power limited Use minimum 0 25 spacing 7AH Rechargeable batteries are the largest batter...

Page 6: ...________________ A G Alarm duration Hours 15 Min 0 25 Hour Alarm ________________ H H Battery capacity required for Alarm E F G ________________ AH I Total calculated battery capacity D H ___________...

Page 7: ...it is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the...

Page 8: ...20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1 40 35 6mm 5 10 129 5mm 6 5625 166 7mm 3 25 82 6mm 3 25 82 6mm 3 25 82 6mm 10 5 266 7mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm 13 0 330 2mm 5 10 129 5mm...

Reviews: