AL1024NK1 Installation Guide 

- 7 -

NEC Power-Limited Wiring Requirements for AL1024NK1:

Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit 

wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited 

circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. 

One such example of this is shown below. Your specific application may require different conduit knockouts to 

be used. Any conduit knockouts may be used. For power- limited applications use of conduit is optional. All field 

wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute).

Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods.

For Canadian installations use shielded wiring for all connections.

Note:

 Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire 

(Fig. 4a).

Fig. 4

Fig. 4a

External

Jacketed

Shield

Incorrect Wire

Handling

Correct Wire

Handling

Pull back

external jacketed

shield approx. 1/2”.

Wire

Insulation

Solid Copper

Conductors

5VDC or 12VDC

Output

VR6

 Input 115VAC 60Hz

(non power-limited)

Optional UL Listed

Battery Enclosure

(non power-limited)

Supervisory,

Fire Alarm

Interface and

Aux. output

Connections

(power-limited)

Battery

Connections

(non power-

limited)

Summary of Contents for AL1024NK1

Page 1: ...4ULXB2 Power Supply Charger 1 VR6 Voltage Regulator Installation Guide Rev 1024NK1_022322 More than just power TM Installing Company ________________ Service Rep Name _________________________________...

Page 2: ...00mA Alarm 10A For Access Control applications battery capacity for 10A supply current 1 hr for 24VDC 12AH battery 6 5 hrs for 24VDC 65AH battery See battery size calculation worksheet for other batte...

Page 3: ...terminals marked OUT on VR6 Fig 2b pg 5 Carefully observe correct polarity 6 For Access Control applications batteries are optional When batteries are not used a loss of AC will result in the loss of...

Page 4: ...esent Contact rating 1A 28VDC AC or brownout fail is reported within 1 minute of event To delay reporting for up to 6 hrs cut AC Delay jumper and reset power to unit Fig 1f pg 4 Bat Fail NC C NO Used...

Page 5: ...y board is factory set for 24VDC Use two 2 12VDC stand by batteries Keep power limited wiring separate from non power limited Use minimum 0 25 spacing 7AH Rechargeable batteries are the largest batter...

Page 6: ...________________ A G Alarm duration Hours 15 Min 0 25 Hour Alarm ________________ H H Battery capacity required for Alarm E F G ________________ AH I Total calculated battery capacity D H ___________...

Page 7: ...it is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the...

Page 8: ...20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1 40 35 6mm 5 10 129 5mm 6 5625 166 7mm 3 25 82 6mm 3 25 82 6mm 3 25 82 6mm 10 5 266 7mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm 13 0 330 2mm 5 10 129 5mm...

Reviews: