17.8 (continued)
An output switch configured for normally open will be open in the normal run state and close
upon a fault.
An output switch configured for normally closed will be closed in the normal run state and will
open upon a fault or loss of 12-24 Vdc input power.
An output switch configured for the ignition module will be open during normal run and will
close upon a fault or loss of 12-24 Vdc input power. Use the NEXT key to make a selection
and press ENTER to save.
NEXT
press to
select
OUTPUT
1
‚
2 3 4
DELAY TIME
‚
3 SEC
N/O N/C
→
IGN
ENTER
press to
accept
the value
change
Upon pressing the ENTER key, a diamond will replace the selection arrow. To view or edit
the next output number, press the NEXT or
→
TENS or
←
TENS keys until the arrow points
to the desired output number and repeat the process.
17.9 To view or edit the hourmeter and servicemeter messages, select “HOURMETER
FUNCTIONS” from the main menu and press ENTER.
EDIT SAFETY SHUTDOWN
6
HOURMETER FUNCTIONS
COMMUNICATIONS
NEXT MENU
ENTER
press to
edit hour-
meter
functions
HOURMETER / SERVICE
MESSAGE NUMBER:
6
00
TOTAL HOURS: 0
RUN TIME HOURS
Message number 00 is the hourmeter labeled as“RUN TIME HOURS”; message numbers
01 through 11 are the servicemeter hours. The servicemeter labels are programmed from
the terminal program using a PC. Use the UNITS and TENS keys to view the run time hours
and the eleven user-programmable service messages. Each service meter message is
displayed on the bottom line. Use the F2 key to reset the hour / servicemeter total hours for
each individual message number.