-22-
17.5 To edit the safety shutdown values, point to “EDIT SAFETY SHUTDOWN” and press the
ENTER key. The edit setpoint values menu is shown. The arrow points to the “EDIT
SETPOINTS”.
ENTER
press to
edit
safety
shutdown
6
EDIT SETPOINTS
VIEW INPUT CLASS
EDIT TEST TIME
OUTPUT CONFIG.
CHAN
6
30
LO SP 20.0 PSIG
HI SP 60.0 PSIG
MANIFOLD PRESSURE
17.6 To view input class, choose “EDIT SAFETY SHUTDOWN” from main menu. Select ‘VIEW
INPUT CLASS” from next menu.
EDIT SETPOINTS
6
VIEW INPUT CLASS
EDIT TEST TIME
OUTPUT CONFIG.
CHAN
6
10
INPUT CLASS A
‚
B C
300 SECONDS TIME
DELAY ON START-UP
Channel 10's input class configuration will be displayed. Each input channel 10-46 can be
either class A, B, or C. The class is programmed in the terminal program using the PC. Both
the high and low setpoints of the analog input channels can be individually set for either
class. On channels 10-27 a diamond next to the input class letter indicates the class for the
displayed channel.