![Altronic DE-2200 Operating Instructions Manual Download Page 20](http://html1.mh-extra.com/html/altronic/de-2200/de-2200_operating-instructions-manual_2913119020.webp)
-20-
17.0 VIEWING OR EDITING THE CONFIGURATION USING THE MENU MODE
17.1 The menu screens can be accessed from any home screen (except test) by pressing the
MENU key. The menu screens allow the user to view or edit safety shutdown functions, the
test time, the hourmeter functions, the time and date, the communications functions, view
the input class and configure the outputs. The monitor must be initially configured using the
terminal program running on a PC connected to the RS-232 port on the back of the monitor.
Reference the programming instructions form DE PI for instructions on how to configure the
monitor system for a specific application. The menu screens are intended to view or edit the
already programmed values in the field. Changes made in the menu are stored in
permanent memory and remain fixed until changed again. Listed below are the values that
can be viewed or edited:
A:
EDIT SAFETY SHUTDOWN:
1.
VIEW OR EDIT SETPOINTS.
-
Edit analog setpoints 30-46
2.
VIEW INPUT CLASS:
-
Class A - no time delay on start-up.
-
Class B - 10 to 999 seconds time delay on start-up before input is active.
-
Class C - 1 to 999 minutes safe-until-first-met with a global time delay.
3.
VIEW OR EDIT TEST TIME - from 1 to 999 seconds.
4.
VIEW OR EDIT THE OUTPUT CONFIGURATION:
-
N/O (Normally Open) - open in the normal run state and closes upon a fault
-
N/C (Normally Closed) - closed in the normal run state and opens upon a
fault or loss of 12-24 Vdc input power.
-
IGN (Ignition Shorting and Fuel Valve Trip Module, Altronic P/N 691124) -
open in the normal run state and closes upon a fault or loss of 12-24 Vdc.
5.
ACTIVATION DELAY TIME - from 0 to 99 seconds.
B:
HOURMETER FUNCTIONS:
1.
VIEW OR EDIT HOURMETER FUNCTIONS - 00 through 11
C:
COMMUNICATIONS:
1.
NODE NUMBER - from 1 to 99 (default is 1).
2.
PORT 1 - ASCII OR MODBUS RTU
2.
PORT 3 - ASCII OR MODBUS RTU
D:
VIEW or EDIT THE TIME AND DATE:
1.
TIME or DATE
E:
VIEW FIRMWARE REVISION
1.
DISPLAY:
2.
TERMINAL: