17.8 (continued)
OUTPUT
6
1 2 3 4
DELAY TIME 0 SEC
N/O N/C
‚
IGN
A selection arrow pointing to output 1 along with output 1’s delay time and a diamond
showing whether it is configured for N/O (normally open), N/C (normally closed), or IGN
(ignition output module 691124) will be shown. To view an output’s configuration, use the
NEXT or
→
TENS or
←
TENS keys to place the selection arrow in front of the output to be
viewed.
The output’s time delay and output state will be shown for each output.
To edit an output’s configuration, use the NEXT or
→
TENS or
←
TENS keys to place the
selection arrow in front of the desired output and press the ENTER key. The selection arrow
will point to the delay time. Each output switch can have its own activation delay time from
0 to 999 seconds. An output switch with a delay time of 0 seconds will trip immediately upon
a fault. If a delay time is set for an output switch, the output will trip following a fault plus the
delay time selected. This allows, for example, a delay time between when the fuel valve trips
on output 1 and when the ignition shorts on output 2.
NEXT
press
OUTPUT 1
→
2 3
4
DELAY TIME 2 SEC
N/O N/C
‚
IGN
ENTER
then
press
A diamond will replace the arrow in front of the selected output switch. An arrow will proceed
the delay time indicating a change can be made to the selected output’s delay time. Use the
↑
UNITS or
↓
UNITS keys to increase or decrease the value by one or use the
→
TENS or
←
TENS key to increase or decrease the value by ten. The ENTER key accepts the change
and advances the pointer to select either N/O, N/C or IGN.
OUTPUT
1
‚
2 3
4
DELAY TIME
→
3 SEC
N/O N/C
‚
IGN
ENTER
press to
accept
the value
change
The selection arrow replaces the diamond indicating a change can be made. The selected
output switch can be configured for N/O (normally open), N/C (normally closed), or IGN
(ignition module 691124).
NOTE: The IGN selection is intended for the Altronic output module 691124 only. The IGN
selection can be made for output switch numbers 1 and 2 only.