
GM 140
page 4
of 12
File: GM140_r0eng - October 2003 - Technical note: GM 140
GM 140
File: GM140_r0eng - October 2003 - Technical note: GM 140
page 5
of 12
Environmental conditions
Use:
Indoor use only
Altitude:
Tested up to 2,000 m
Temperature:
5°C to 30°C
Relative Humidity:
80% for temperature up 31°C,
linearly decreasing to 50%
RH at 40°C
Pollution degree:
2 according IEC664
Fuses
The equipment is provided with 4 fuses on the interface
board (inside the generator) installed on the front panel.
IO board fuse
Dimension, type:
6x32 mm, ceramic,
Rupturing speed:
Time - F
Rated current:
F1, F2 and F3: 5 A
F4: 500 mA
Rated voltage:
500 V
Physical characteristics
Total lenght:
610 mm
Total width:
200 mm
Cabinet width:
160 mm
Cabinet height:
180 mm
Total weight:
12 kg (26 lbs)
Equipment installation
The GM140 cannot operate stand alone: it must be coupled
to a proper cavity by the R26 flange.
The equipment cannot operate cantilevered, it must be sa-
fely fixed vertically. If used horizzontally you must provide
a suitable support.
Handling instructions
During handling use always protection gloves. The equip-
ment doesn't have lifting eyebolts and its weight is 12 kg
(26 lbs): always lift the equipment using only the bottom of
the cabinet with a proper lifting apparatus.
Do not add any eyebolt to the cover or the front panels: they
are not suitable for lifting operations.
Wiring instructions
The GM140 must be installed and serviced only by quali-
fied personnel acquainted with the regulations covering the
application.
For safety operations the following rules must be adopted:
I) the equipment must be grounded by the connector
CONN#1 using the pin n° 4 (see the wiring drawings at
page 10 and 11);
II) the three phase main supply, type phase/phase/phase/
must be provided by connector CONN#1: phase connection
to pin 1,2 and 3, ground to pin 4;
III) the connector's pins can house wires up to 2.5 mm
2
; the
wires lenght shall be according to current capability of the
wires section;
IV) the user must provide external circuit breaker and ther-
mal cut-off. These devices must protect the GM140 from
short-circuit and thermal runaway;
V) these external protection devices must allow to switch-
off the main line for maintenance operations;
VI) the external circuit breaker must be a three poles
breaker and comply the norm EN61010-1;
VII) the external circuit breaker must be in close proximity
to the GM140 and within easy reach of the operator;
VIII) the external circuit breaker must be marked as the
disconnecting device for the GM140;
IX) the connector CONN#1 must never be used as a switch-
off device.
X) the signals must be provided by CONN#3 with 25 poles
flat cable (according to wiring diagram at page 10 and 11).
XI) the reference signal to adjust power must by provided
by CONN#2 with a 9 poles flat cable (according to wiring
diagram at page 10 and 11).
Operating Controls
The GM140 is driven through electrical signals at
connectors.
CONN#1
Power supply
CONN#2
Pin 1-2 SET VALUE FOR MW POWER reference signal
for microwave power (SetPoint).
0÷10Vdc / 0÷100% Power. No power is emitted unless you
reach a reference signal of 1Vdc (10% power).
CONN#3
Controls. Optoinsulated signals.