insulating the hydraulic con-
nections
note.
Insulate the heating circuit and the heat
source according to local applicable
standards and directives.
The angle ball valves of the connections on the module
box must be opened.
check seals of all hydraulic connections. conduct
pressure test…
Remove insulation material for internal pipes from
the extra box.
Insulate all connections, angle ball valves, vibration
decouplers, connections and lines of the heat source
in the unit so that they are moistureproof..
Overflow valve
inspeCting and setting up the overflow valve
note.
Make sure to perform the following steps
within a relatively short time. the heat
pump switches to high-pressure fault if
the maximum return flow temperature is
exceeded.
make sure that the system is running in heating
mode (ideally in cold condition)…
With the heating curve set low, switch the system
to “forced heating”…
operating manual of the heating and heat pump
regulator.
Shut off valves to heating circuit…
make sure that the volume flow is channelled 100%
through the overflow valve…
Read the forward flow and return flow temperatures
in the heating and heat pump regulator…
operating manual of the heating and heat pump
regulator.
Turn the adjusting knob of the overflow valve until
the temperature difference (= spread) between the
forward and return flow is between 5 and 9 K...
1 Adjusting knob
2 overflow valve
note.
turning the adjusting knob:
– clockwise = increases spread.
– anticlockwise = decreases spread.
open valves to heating circuit.
Reset the heating and heat pump regulator.