 CautIon!

 

Insert all three connecting plugs of the 
module box in the plug-in connections on 
the bottom of the intermediate floor of the 
unit. Watch out for retaining nose. plugs 
must be mounted for easy movement…

  open electrical switch cabinet of unit…

 

To do this, only loosen the two upper screws of the 
cover plate. Remove the remaining screws. Now the 
cover plate can be removed…

  Insert load lines and external control and sensor 

wires in unit through holes at top for electric/
sensor wires. Guide wires via the cable duct to the 
terminals. Tighten strain relief screws.

 Install electrical connections according to the 

terminal diagram and the circuit diagrams.

  „“Terminal diagram” and “circuit diagrams”.

 WarnIng!

 

Install electric connections only according 
to the terminal diagram and the circuit 
diagrams that apply to your model.

 CautIon.

 

the power supply for the heat pump 
and the electric heating element must 
be equipped with a 3-phase automatic 
circuit-breaker with at least 3mm contact 
spacing to IeC 60947-2.

 

note the level of the trigger current.

 overview “Technical data / scope of delivery”, 

“electric” section.

electrical connections

The following applies to all work to be done:

 Danger!

 

risk of fatal injury due to electric shock!

 

electrical connections may be installed 
only by qualified electricians.

 

Before opening the unit, disconnect the 
system from the power supply and secure 
it from being switched back on!

 Danger!

 

Comply with the local regulations and 
standards when installing and carrying out 
electrical work.

 

Comply with technical connection 
requirements of the responsible power 
supply company (if required by the latter)!

 note.

 

all live wires must be stripped before they 
are installed in the cable duct of the switch 
cabinets!

  Remove front panel of unit, if necessary. 

  Transport to installation location,  .

1  penetrations for electric/sensor 

cables with strain relief screws

2  electrical switch cabinet
3  Intermediate floor of unit

  connect connecting plug of module box…

Summary of Contents for WZS Series

Page 1: ...e right to modify technical specifications without prior notice UK830637 210804 Translation of the operating manual Alpha InnoTec GmbH Heat pumps Operating Manual Brine heat station Brine Water UK WZS...

Page 2: ...s comply with the parameters for the respective model This operating manual is intended only for persons assigned to work on or operate the unit Treat all constituent parts confidentially The informat...

Page 3: ...erheitsbaugruppe 15 Ausdehungsgef sse 15 Elektrische Anschlussarbeiten 16 Sp len und Bef llen der Anlage 18 Sp len und bef llen der W rmequelle 18 Sp len und bef llen des Heiz und Brauchwarmwasserlade...

Page 4: ...afety The unit is safe to operate for its intended use The construction and design of the unit conform to current state of the art standards all relevant regulations and all relevant safety regulation...

Page 5: ...ian or the manufacturer s local partner Overview Customer service Warranty Guarantee For warranty and guarantee conditions please refer to the purchase documents Note Please contact your dealer concer...

Page 6: ...ideration the ambient conditions limits of application and the applicable regulations every heat pump can be utilised in new or existing heating systems Overview Technical data scope of delivery Opera...

Page 7: ...pumps filters dirt traps should be inspected as well as cleaned as needed at the very least annually by a qualified heating or cooling system technician Regularly check that the safety valve for the...

Page 8: ...urce 10 Module box with integrated circulating pump of heat source Complete the following first Inspect the delivery for outwardly visible signs of damage Check to make sure that the delivery is compl...

Page 9: ...e extra box and module box from the wooden pallet and bring to installation location Use straps to lift and carry the module box Caution Do not tilt the module box more than a maximum of 45 in any dir...

Page 10: ...ng tasks Mount one foot each on the front and back of the unit 1 Foot 2 Lock nut 3 Adjusting screw Transport unit to installation location using a hand truck or have two persons carry it Caution Do no...

Page 11: ...r feet of the module box that are facing the unit come to rest on the centring plate behind the front edger of the bottom of the unit Push module box into the unit until the front rubber foot of the m...

Page 12: ...can be flushed if necessary Caution The condenser may be flushed only by customer service personnel authorised by the manufacture Caution During connection of components secure connections on the modu...

Page 13: ...on on left side of unit 2 Connection on right side of unit Proceed as follows Cut out round plates on the desired connection side Remove the tags cleanly so that no metal burrs remain Cut foam with a...

Page 14: ...When tightening the connections on the module box always secure connections against twisting Insert included plastic rosettes in the holes Insert vibration decouplers in unit from outside and guide t...

Page 15: ...ic hot water tank according to the relevant local standards and guidelines Caution Do not exceed the operating pressures specified on the rating plate Install a pressure reducer if necessary Opening t...

Page 16: ...to your model Caution The power supply for the heat pump and the electric heating element must be equipped with a 3 phase automatic circuit breaker with at least 3mm contact spacing to IEC 60947 2 No...

Page 17: ...s for sensors pumps Terminal diagram circuit diagram for respective model Note The control element of the heat and heat pump regulator can be connected with a computer or network using an network cabl...

Page 18: ...freeze in the water must be at the level specified for your model Overview Technical data scope of delivery Heat source section Fill heat source with anti freeze mixture Flushing and filling the unit...

Page 19: ...switch for 2 way valve Note To ensure a good seat of the motor on the valve make sure that the U bolt with the reduction is not pushed past the lug because then the motor will not be held securely on...

Page 20: ...ater inlet valve on domestic hot water tank Open the domestic hot water valves at the taps Flush the domestic hot water tank until no more air discharges from the valves at the taps Close domestic hot...

Page 21: ...llowing steps within a relatively short time The heat pump switches to high pressure fault if the maximum return flow temperature is exceeded Make sure that the system is running in heating mode ideal...

Page 22: ...nt heights in the front fa ade of the unit are recesses each with 4 recesses for the fastening of the control element 1 four upper recesses 2 four lower recesses 4 hooks are located on the back of the...

Page 23: ...etwork cable s RJ 45 plug into the left bushing of the control element Note The network cable can be retrofitted at any time However in order to be able to connect it the screen must first be removed...

Page 24: ...ct a thorough installation inspection and go through the items on the general checklist General checklist The installation inspection will prevent damage to the heat pump system that could be caused b...

Page 25: ...set knob Dismantling Danger Risk of fatal injury due to electric shock Electrical connections may be installed only by qualified electricians Before opening the unit disconnect the system from the pow...

Page 26: ...ttery can be removed using a side cutter Dispose of battery and electronic components in keeping with environmental considerations Removal of the module box Proceed as follows Remove insulation Close...

Page 27: ...27 We reserve the right to modify technical specifications without prior notice UK830637 210804 Translation of the operating manual Alpha InnoTec GmbH...

Page 28: ...de integriert Brauchwarmwassertemperatur bis C Sch ttleistung 38 C 45 C bei Entnahme von 10 l min l l Anschl sse Brauchwarmwasser Elektrik Spannungscode allpolige Absicherung W rmepumpe A Spannungscod...

Page 29: ...0 5 25 1 5 813425 WZS 80H SX 8 4 4 2 8 0 3 3 8 5 4 3 20 61 5 25 B0 W65 37 49 1500 2000 2500 0 36 1500 25 13 750 1400 1700 0 35 1000 1 290 200 90 R1 AG G1 WM DIN ISO 228 R407c 1 8 195 52 250 210 R 3 4...

Page 30: ...zleistung Pe Leistungsaufnahme COP Coeffiicient of performance Leistungszahl p Freie Pressung Heizkreis p Freie Pressung W rmequelle We reserve the right to modify technical specifications without pri...

Page 31: ...zleistung Pe Leistungsaufnahme COP Coeffiicient of performance Leistungszahl p Freie Pressung Heizkreis p Freie Pressung W rmequelle We reserve the right to modify technical specifications without pri...

Page 32: ...zleistung Pe Leistungsaufnahme COP Coeffiicient of performance Leistungszahl p Freie Pressung Heizkreis p Freie Pressung W rmequelle We reserve the right to modify technical specifications without pri...

Page 33: ...zleistung Pe Leistungsaufnahme COP Coeffiicient of performance Leistungszahl p Freie Pressung Heizkreis p Freie Pressung W rmequelle We reserve the right to modify technical specifications without pri...

Page 34: ...hlweise rechts oder links G1 3 Heizwasser Eintritt R cklauf R1 4 Heizwasser Austritt Vorlauf R1 5 Brauchwarmwasser R3 4 6 Kaltwasser R3 4 7 Durchf hrung f r Elektro F hlerkabel 8 Bedienteil im Beipack...

Page 35: ...Freiraum f r funktionsnotwendiges Zubeh r FS Freiraum f r Servicezwecke OKF Oberkante Fertigfu boden V1 Version 1 V2 Version 2 We reserve the right to modify technical specifications without prior not...

Page 36: ...36 We reserve the right to modify technical specifications without prior notice UK830637 210804 Translation of the operating manual Alpha InnoTec GmbH Terminal diagram WZS 41H SX WZS 100H SX...

Page 37: ...37 We reserve the right to modify technical specifications without prior notice UK830637 210804 Translation of the operating manual Alpha InnoTec GmbH WZS 41H SX Circuit diagram 1 2...

Page 38: ...38 We reserve the right to modify technical specifications without prior notice UK830637 210804 Translation of the operating manual Alpha InnoTec GmbH Circuit diagram 2 2 WZS 41H SX...

Page 39: ...39 We reserve the right to modify technical specifications without prior notice UK830637 210804 Translation of the operating manual Alpha InnoTec GmbH WZS 60H SX WZS 100H SX Circuit diagram 1 2...

Page 40: ...40 We reserve the right to modify technical specifications without prior notice UK830637 210804 Translation of the operating manual Alpha InnoTec GmbH Circuit diagram 2 2 WZS 60H SX WZS 100H SX...

Page 41: ...0 596 WZS 60H SX 100 597 WZS 80H SX 100 598 WZS 100H SX 100 599 EG Richtlinien Harmonisierte EN 2006 42 EG EN 378 EN 349 2006 95 EG EN 60529 EN 60335 1 2 40 2004 108 EG EN ISO 12100 1 2 EN 55014 1 2 E...

Page 42: ......

Page 43: ...43 We reserve the right to modify technical specifications without prior notice UK830637 210804 Translation of the operating manual Alpha InnoTec GmbH...

Page 44: ......

Page 45: ...45 We reserve the right to modify technical specifications without prior notice UK830637 210804 Translation of the operating manual Alpha InnoTec GmbH...

Page 46: ...oTec Schweiz AG Via alla Torre 2 6850 Mendriso Tel 41 0 91 646 08 81 Fax 41 0 91 646 09 91 info alpha innotec ch www alpha innotec ch CZ SK Tepeln cerpadla AIT s r o n m Republiky 15 614 00 Brno Tel 4...

Page 47: ...nathan nl www nathan nl NO Alpha InnoTec Norge AS Gamle Forusveien 51b 4033 Stavanger Tel 47 0 51 6605 95 Fax 47 0 51 6605 94 info alpha innotec no www alpha innotec no PL Hydro Tech ul Zak adowa 4D 6...

Page 48: ......

Reviews: