Tri Power X33 TE 10/20/30/40/60 kVA
26
60kVA Power Terminal Positions
Maximum Current
Input/ Output
Voltage
Output Power
Maximum
Input
Current
(1)
Max.
Output/ Bypass
Input Current
(2)
Max. Battery
Discharge
Current
(3)
380 V
10kVA/10KW
19 A
15 A
35 A
20kVA/20KW
38 A
30 A
69 A
30kVA/30KW
57 A
46 A
103 A
40kVA/40KW
75 A
61 A
137 A
60kVA/60KW
113 A
91 A
206 A
400 V
10kVA/10KW
18 A
14 A
35 A
20kVA/20KW
36 A
29 A
69 A
30kVA/30KW
54 A
43 A
103 A
40kVA/40KW
72 A
58 A
137 A
60kVA/60KW
108 A
87 A
206 A
415 V
10kVA/10KW
17 A
14 A
35 A
20kVA/20KW
35 A
28 A
69 A
30kVA/30KW
52 A
42 A
103 A
40kVA/40KW
69 A
56 A
137 A
60kVA/60KW
104 A
83 A
206 A
(1)
The UPS is operating at rated voltage, rated power and batteries are charging but
regardless of the overload.
(2)
The UPS is operating at rated voltage and rated power but regardless of the overload.
(3)
12Vbattery blocks
×
32pcs. The UPS is operating at rated voltage and rated power but
regardless of the overload.
Output
Mains/ Bypass
Battery