Tri Power X33 TE 10/20/30/40/60 kVA
23
2-3
General Requirement for Ventilation and Maintenance
During installation ensure that the following conditions are met.
Keep at least 1000 mm of free space in front of the UPS for air flow and future
maintenance purposes.
Keep at least 300mm of free space in rear of the UPS for air-flow space.
Keep at least 500mm of free space in the top of UPS for maintenance operations.
Front Side
>1000mm
Rear Side
>300mm
Top Side
>500mm
UPS
Other
Equipment