Alpha CombiMax 350 and 600
4.4
FIT THE COMBIMAX - Figs. 7 and 8
1.
Locate the wall mounting frame over the top left hand panel of the combination boiler to ensure correct alignment.
2.
Drill five wall fixing holes (8 mm dia.) through the mounting frame (as shown in Fig. 7) and secure with the screws and
plugs provided.
3.
Hang the storage cylinder on the mounting frame, ensuring the top and bottom brackets on the store locate on the supports
on the frame (see Fig. 7). Pass the plastic security strap around the cylinder and secure in position (see Figs. 7 and 8).
4.
Connect the flexible hose to the expansion vessel and locate it in the space above the boiler to the rear, with the connection
to the left as shown in Fig. 8. Connect the expansion vessel hose to the connection on the top left hand side of the store.
CombiMax 600 only - Secure the vessel to the right side rear of the boiler frame with the two screws provided.
5.
Fit the side support bracket to the boiler in place of the boiler left hand side panel, securing at both top and bottom as
shown in Fig. 8 (remove the front screw from the top of the room sealed chamber to secure the top of the bracket).
6.
Fit the top support bracket (with two clips) to the top of the side support bracket and fit the bottom support bracket (with
four clips) to the bottom of the side support using the screws provided.
7.
Fit the left hand side panel, removed from the boiler, to the CombiMax by hooking the top of the panel over the brown trim
of the mounting frame and securing it at the bottom rear of the panel. Secure the panel to the top and bottom support
brackets using the screws provided.
Fig. 7
Fig. 8
4.5
FIT THE FLUE
Install the flue in accordance with the Installation instructions supplied with the boiler or flue.
4.6
CONNECT THE PIPEWORK - Fig. 9
1.
Thoroughly flush out all the water pipework.
Note: Ensure that all the plastic caps are removed from the boiler connections.
2.
Secure all the valves/fittings between the CombiMax and boiler as shown in Fig. 9. Use the washers supplied and ensure
the necessary fittings face the rear wall. Fit the union bends to the valves.
Notes: a. If soldering to the boiler union bends, ensure the bends are not connected to the valves, otherwise the internal
seals may be damaged.
b. Ensure the 22 mm isolating valve with the filter is fitted to the heating return connection as shown in Fig. 9.
c. Fit the pressure relief valve connection before the isolating valves.
3.
Connect the system pipework to the boiler.
Note: Do not forget that the heating system pressure relief valve discharge pipe must be routed clear of the boiler to a
drain in such a manner that it may be seen, but cannot cause injury to persons or property.
4.
Connect the discharge pipework from the temperature/pressure relief and expansion relief valves to the tundish supplied.
Note: This pipework must be installed as recommended in Unvented Hot Water Storage System, section 3.4.