010-619-J0 Rev B
Page 41
8
System Startup
8.1
Check System Connections
•
Ensure AC is off, battery is disconnected, and all power modules are removed from the shelf.
•
Verify the polarity of all connections.
8.2
Verify AC and Power The Shelf
•
Install one power module.
•
Verify AC input voltage is correct and turn on the corresponding AC input feeder breaker.
•
The power module OK LED should illuminate after a preset start delay.
•
Using the controller, test functionality of various module alarms and controls.
8.3
Check Battery Polarity and Connect
•
Verify correct battery polarity using a voltmeter (ensuring no cells or batteries are reversed).
•
Connect battery as required to the output of the system or turn on battery breaker.
•
Install remaining power modules.
•
On the controller, set Float and Equalize voltage to the levels specified by the battery manufac-
turer.
•
For some systems, the default setting for low AC voltage alarming is 180Vac. For nominal 120Vac
operation, it is recommended to reset this value to 100Vac.
•
Using the controller, test the functionality of various module alarms and controls. In addition,
perform a load test with the system using a resistive load box as needed.
8.4
Controller Reset
8.4.1
Soft Reset (CXCM1+ only)
The reset button located on the front panel of the CXCM1+ is for restarting the microprocessor. When
pressed momentarily, the unit beeps twice then resets. The front-panel LEDs illuminate temporarily, and
then extinguish after the system has finished its 15-second self-test.
NOTE
:
This does not apply to the CXCM1 HP.
8.4.2
IP Address Reset (CXCM1+ only)
To reset the IP address, press and hold the front panel reset button for three seconds. The CXCM1+
unit beeps three times, IP address resets to 10.10.10.201 and DHCP is disabled. The settings are saved
and the unit then resets.
This reset allows local access; e.g., with a laptop and a standard network crossover cable. See current
version software manual for details.
NOTE
:
This does not apply to the CXCM1 HP.
Summary of Contents for Cordex HP 48 1.2kW
Page 2: ......
Page 4: ......
Page 10: ...vi...
Page 14: ...010 619 J0 Rev B Page 4...
Page 16: ...010 619 J0 Rev B Page 6 Figure 1 Single Shelf Figure 2 Dual Shelf Figure 3 2RU Shelf...
Page 28: ...010 619 J0 Rev B Page 18...
Page 30: ...010 619 J0 Rev B Page 20...
Page 46: ...010 619 J0 Rev B Page 36...
Page 56: ...010 619 J0 Rev B Page 46...
Page 58: ...010 619 J0 Rev B Page 48...