A USB Port
B Terminal Resistor for Parallel function
C CAN Bus Connection Port for Parallel System
(Do not for telecommunication network)
D Customer Options Slot 1
F Cooling Fan
G External Battery Connector
H External Battery Ground
I
Utility Input Breaker CB1
J
Bypass Input Breaker CB2
L Input/output Terminal Block
N EPO
-
Emergency Power Off
-
: 2 types switch state, Normal Close
and Normal Open
EPO can be converted to ROO
(Remote ON/OFF)
ROO with2 types switch state -Normal Close and Normal Open
ROO and EPO need to use the software switching
Q
Temp. Comp.
2.4. Communication Port
2.4.1. The communication port on the UPS provides for USB communication with
the UPS software to remotely monitor the power and UPS status.
2.4.1.1. You may use optional interfaces cards for R2E (RS-232), RSE (RS-485),
USE (second USB), DCE (Dry Contact), and SNMP. However, the R2E
card, RSE card and USE card must not be used simultaneously.
2.4.1.2. The software bundled with the UPS is compatible with many operating
systems such as Windows 2000, XP, Server 2003, VISTA, Server 2008,
Win7 and Win8. For other applications such as Novell NetWare, Unix, or
Linux please contact your local distributor for a proper solution.
2.4.1.3. When the optional interface cards are used together with the onboard
USB port the EPO signals will get highest priority, then the SNMP/WEB
card, then the shutdown command at the DCE, R2E, RSE, and USE
cards, and then finally the onboard USB port gets the lowest priority.
2.4.2. USB Definition:
2.4.2.1. complies with USB version 1.0,1.5 Mbps
2.4.2.2. complies with USB HID version 1.0
2.4.2.3. Pin Assignments:
1
VCC (+5V)
2
D
-
3
D
-
4
Ground
Page
15
to
4
5
Page
14
to
4
5