22
Subject to change without notice | 83061500aUK – Translation into English of the original German operating manual | ait-deutschland GmbH
SETTING THE OVERFLOW VALVE
Open the overflow valve fully, close heating circuits
Switch the „Set overflow valve“ menu item from No“
to „Yes“; the circulation pump is then activated with
100% – the pump starts up.
If the control signal UWP 100% has been reached,
close the changeover valve so that the maximal flow
can be ensured (see technical data).
After leaving the „Set overflow valve“ menu or after 1
hour at the latest the circulation pump switches back
to default control
Valves for heating open
Dismantling
DANGER!
Risk of fatal electric shock!
All electrical connection work must be
carried out by qualified electricians only.
Before opening the unit, disconnect the sys-
tem from the power supply - wait for 90 sec-
onds = residual voltage at inverter - and pre-
vent it from being switched back on again!
WARNING!
Only qualified heating or cooling system
personnel are allowed to remove the unit
from the system.
ATTENTION
Recycle or ensure proper disposal of unit compo-
nents, refrigerants and oil according to the relevant
regulations, standards and guidelines.
REMOVAL OF THE BUFFER BATTERY
ATTENTION
Before scrapping the heating and heat pump con-
troller, remove the buffer battery on the proces-
sor board. The battery can be pushed out using a
screwdriver. Dispose of the battery and electronic
components in an environmentally friendly way.
Overflow valve
TESTING AND SETTING THE OVERFLOW VALVE (ONLY
NECESSARY FOR INTEGRATION OF STORAGE TANK IN
SERIES)
In the IBN Wizard it is possible to set the overflow valve
according to the hydraulic system for integration of storage
tanks connected in series.
Confirm IBN Wizard or make the setting via:
Service >> Settings >> Efficiency pump
The „Set overflow valve“ menu item is pre-set to „No“. The
overflow valve setting function is deactivated.
•
Control signal UWP is the display of the currently re-
quested pump delivery in %
•
Actual flow is the current flow (measuring accuracy
+/- 200l/h)