Performance data
Values in brackets: (1 Compressor)
Jersey 5
Jersey 7
Heating capacity | COP
for A10/W35 acc. to DIN EN 14511-x
Partial load operation
kW | COP
2.95 | 6.00
4.49 | 5.34
for A7/W35 acc. to DIN EN 14511-x
Partial load operation
kW | COP
2.61 | 5.03
3.92 | 4.61
for A7/W55 acc. to DIN EN 14511-x
Partial load operation
kW | COP
2.39 | 2.71
3.22 | 2.66
for A2/W35 acc. to DIN EN 14511-x
Partial load operation
kW | COP
2.32 | 4.20
5.11 | 3.76
for A-7/W35 acc. to DIN EN 14511-x
Full load operation
kW | COP
4.64 | 2.57
7.21 | 2.68
for A-7/W55 acc. to DIN EN 14511-x
Full load operation
kW | COP
4.33 | 1.83
6.68 | 2.00
Heating capacity
for A10/W35
min. I max.
kW | kW
2.95 | 8.75
4.49 | 10.57
for A7/W35
min. I max.
kW | kW
2.67 | 7.06
3.85 | 8.87
for A7/W55
min. I max.
kW | kW
1.88 | 6.81
3.50 | 8.21
for A2/W35
min. I max.
kW | kW
2.32 | 4.24
2.60 | 6.60
for A-7/W35
min. I max.
kW | kW
1.69 | 4.64
2.10 | 7.21
for A-7/W55
min. I max.
kW | kW
0.96 | 2.87
1.90 | 6.68
Cooling capacity | EER
for A35/W18
Partial load operation
kW | EER
3.56 | 5.36
5.30 | 5.33
for A35/W7
Partial load operation
kW | EER
- | -
- | -
Cooling capacity
for A35/W18
min. I max.
kW | kW
3.56 | 7.16
5.30 | 10.44
for A35/W7
min. I max.
kW | kW
- | -
- | -
Heating capacity domestic hot water preparation
kW
-
-
Operating limits
Heating circuit return min. | Heating circuit flow max. Heating
within heat source min./max.
°C
20 | 55
20 | 55
Heat source, heating
min. I max.
°C
-20 | 40
-20 | 40
Additional operating points
…
-
-
Installation location
(only valid for indoor installation)
Room temperature
min. I max.
°C
- | -
- | -
Relative humidity maximum (non-condensing)
%
-
-
Sound
Sound power level inside
min. | Night | max.
dB(A)
- | - | -
- | - | -
Sound power level outside
1)
min. | Night | max.
dB(A)
48 | 48 | 62
55 | 55 | 62
Sound power level acc. to DIN EN 12102-1
inside | outside
dB(A)
- | 51
- | 55
Tonality | Low-frequency
dB(A) | • yes – no
0 | –
0 | –
Heat source
Air flow rate at maximum external pressing | Maximum external pressure
m³/h | Pa
2530 | 0
3000 | -
Heating circuit
Flow rate (pipe dimensioning) I Min. volume buffer tank in series I Min. volume separation buffer tank
l/h | l | l
1044 | 20 | 20
1368 | 20 | 20
Free pressing | Pressure loss | Flow rate
bar | bar | l/h
0.381 | 0.152 | 1044
0.408 | 0.176 | 1368
Max. allowable operating pressure
bar
3
3
Circulation pump control range
min. I max.
l/h
100 | 1800
100 | 1800
General unit data
Data of the standards according to version
EN14511-x I DIN EN 12102-1
2019 | 2018
2019 I 2018
Total weight
kg
82,00
103,00
Weight of heat pump module | Compact module | Fan module
kg | kg | kg
82 | - | -
103 | - | -
Refrigerant type | Refrigerant capacity
… | kg
R410A | 1.5
R410A | 2.55
Electrics
Voltage code | all-pole fuse protection for heat pump *)**)
… | A
1~N/PE/230V/50Hz | B16
1~N/PE/230V/50Hz | B16
Voltage code | Control voltage fuse protection **)
… | A
-
-
Voltage code | Electric heating element fuse protection **)
1 phase
… | A
- | -
- | -
Voltage code | Electric heating element fuse protection **)
3 phases
… | A
- | -
- | -
HP*): effect. power consumption A7/W35 (partial load operation) DIN EN 14511-x I Electric consumption I cosφ
kW | A | …
0.50 | 2.3 | 0.97
0.87 | 3.8 | 0.97
HP*): effective power consumption A7/W35 acc. to DIN EN 14511-x: min. I max.
kW | kW
0.50 | 1.95
0.82 | 2.00
HP*): max. machine current I max. power consumption within the operating limits
A | kW
15 | 3.35
16 | 3.5
Starting current: direct | with soft starter
A | A
< 5 | -
< 5 | -
Degree of protection
IP
24
24
Zmax
Ω
-
-
Residual current circuit breaker
if required
type
B
B
Electric heating element output
3 | 2 | 1 phase
kW | kW | kW
- | - | -
- | - | -
Circulation pump power consumption, heating circuit
min. I max.
W
- | -
- | -
Other unit information
Safety valve heating circuit | Response pressure
included in scope of supply: • yes – no | bar
– | –
– | –
Buffer tank | Volume
included in scope of supply: • yes – no | l
– | 0
– | 0
Heating circuit expansion vessel | Volume | Prepressure
incl. in scope of supply: • yes – no | l | bar
– | – | –
– | – | –
Overflow valve | Changeover valve, heating - domestic hot water
integrated: • yes – no
– | –
– | –
Heating circuit vibration decoupling
incl. in scope of supply or integrated: • yes – no
•
•
Controller I Heat quantity recording I Extension board
incl. in scope of supply or integrated: • yes – no
• | • | –
• | • | –
813640
813641
*) compressor only, **) note local regulations 1) Indoor and outdoor installation.
The performance data and the operating limits apply to clean heat exchangers l Index: k
Technical data / Scope of supply
Jersey