Other Applications
Alternative System Requirements
The ICS Plus can be used in systems with varying requirements, or with third-party equipment. Some
systems may only need certain ICS Plus components, rather than the entire system. This may depend
on the applicable codes.
NOTE:
All systems depicted here assume the use of a PV combiner with AFCI protection required.
Table 2
Applications
PV Application
Combiner
and AFCI
PVRSS
Initiator
System Power
Load Center
Disconnect
These battery-based applications use OutBack equipment, or equipment which operates in the equivalent voltage range.
300 Vdc max array
24 to 48 Vdc battery bank
PVRSS required
FWPV6-FH600-SDA RSI
BKR-CTRL-DC
PNL-75*-DC-RT
* 75, 75D, or 75Q
300 Vdc max array
24 to 48 Vdc battery bank
PVRSS NOT required
FWPV6-FH600-SDA
—
BKR-CTRL-DC
—
These battery-based applications may require third-party equipment which operates in higher voltage ranges.
300 to 600 Vdc max array
24 to 48 Vdc battery bank
PVRSS required
FWPV6-FH600-SDA RSI
BKR-CTRL-DC
Third-party PVRSE
rated for 600Vdc
300 to 600 Vdc max array
24 to 48 Vdc battery bank
PVRSS NOT required
FWPV6-FH600-SDA
—
BKR-CTRL-DC
—
These non-battery-based applications may require third-party equipment which operates in higher voltage ranges.
600 Vdc max array
Non-battery-based system
PVRSS required
FWPV6-FH600-SDA RSI
Isolated Class 2 DC supply
Up to 15 Adc
24 Vdc ± 3% maximum
(over operating
conditions)
PVRSE rated for
600Vdc
600 Vdc max array
Non-battery-based system
PVRSS NOT required
FWPV6-FH600-SDA —
—
IMPORTANT:
When BKR-CTRL-DC is not used and no
J4
input is provided to the RSI,
J4
must have pins
1 and 2 connected together with a jumper. (See page 16.) This provides the RSI Safe signal
that otherwise would not be present.