__________________________________________________________________________________
Alpha ESS Co., Ltd.
Page 26 of 59
Your Smart Energy
Installation
Figure 4.1 Installation position limit
A
“
≥1,000mm, ensure that the front door of the cabinet can be fully opened. There is
sufficient space for cold air to enter. Users can conveniently insert and extract the
module and operate.”
B
"≥500mm, ventilation and heat dissipation should be ensured. Users can have
sufficient space for maintenance."
C, D
"
≥1,000mm, ensure that the sides of the cabinet can be fully accessed. Ventilation
and heat dissipation should be ensured. Users can have sufficient space for
maintenance."
The final installed position of the T30 should have the minimum distances from any peripheral
walls as highlighted in the above table to ensure that the doors can be fully opened and closed,
and the side panels can be accessed conveniently. There should also be sufficient space for
m
odule insertion and extraction, normal heat dissipation and user’s operation.
4.3.1.2 Positioning Steps
Step1
:
Remove the cabinet from the delivery truck using a forklift truck or suitable lifting tool
as per Figure 4.2.
Note: In an environment with sufficient space.