Fault Name
Troubleshooting
Fault
Category
BMS
LCD Fault
Display
Commu_fail_LMU
LMU
Communication
fault
Check if the communication cable
connector between the
HV-control box and the battery is
not plugged in.
If the problem is not resolved,
please contact AlphaESS customer
service.
Cell-Ov-Temp
Cell over
temperature fault
Stop charging and discharging and
then run the system after the fault
is eliminated.
If the problem is not resolved,
please contact AlphaESS customer
service.
Commu_fail_BMU
BMU
Communication
fault
Check if the communication cable
connector between the
HV-control box and the TOP
BMU is not plugged in.
If the problem is not resolved,
please contact AlphaESS
customer service.
TROUBLESHOOTING
TROUBLESHOOTING
38
39
Troubleshooting
10
Fault Name
Troubleshooting
Fault
Category
BMS
LCD Fault
Display
Cell-Temp-Diff
Cell temperature
different fault
Shut down the system for about
2 hours, then restart the system
to check if the fault is eliminated.
If the problem is not resolved,
please contact AlphaESS
customer service.
Chrg-Ov-Curr
Module charge
over current fault
Restart the system to check if the
fault is eliminated.
If the problem is not resolved,
stop any operation on the system
and contact AlphaESS customer
service.
Disch-Ov-Curr
Module discharge
over current fault
Restart the system, turn off some
of the loads to check if the fault
is eliminated.
If the problem is not resolved,
stop any operation on the system
and contact AlphaESS customer
service.
Pole-Ov-Temp
Pole over
temperature fault
Shut down the system for about
2 hours, then restart the system
to see if the fault is eliminated.
If the problem is not resolved,
please contact AlphaESS
customer service.
Cell-Ov-Volt
Cell over volt fault
Restart the system, switch the
system to the discharging state, If
the error is not eliminated, stop
any operation on the system and
contact AlphaESS customer
service.
Cell-Volt-Diff
Cell volt different
fault
Restart the system to see if the
fault is eliminated.
If the problem is not resolved,
please contact AlphaESS
customer service.
Disch-Low-Temp
Cell discharge
under
temperature fault
Confirm that the ambient
temperature is higher than -10
℃
..
If it is lower than it, please turn
on the heating equipment such as
heater. If the ambient
temperature is higher than -10
℃
.,
restart the system.
If the problem is not resolved,
please contact AlphaESS
customer service
Cell-Low-Volt
Cell under volt
fault
Restart the system to see if the
fault is eliminated
If the problem is not solved,
please contact AlphaESS customer
service
IR_Fail
Insulation
resistance fault
Switch off the battery MCCB and
measure the impedance of the
positive and negative poles of the
battery to the ground to see if it is
greater than 270KΩ and restart
the system.
If the problem is not solved. stop
any operation on the system and
contact AlphaESS customer
service.