2.3 Wiring
Figure 23 Connection of Power Cables on Battery Side
Figure 24 Battery Power Cable
Figure 27 Communication Cables
Figure 25 Power Cable Plug Connectors
Figure 26 Connection of Communication Cables on Battery Side
Step 10
Please hang the HV50056 on the rear bracket of HV50056 and hang the SMILE-T10-INV
on the bracket B of the inverter. Fix them with screws.
Step 1
Before wiring please remove the front maintenance baffle of the batteries with a
cross screwdriver.
Step 2
Please connect the power cables as referred in Figure 21
Step 3
Please connect the communication cables as referred in Figure 24
Battery power cable connection sequence:
Through the waterproof cap→through the sealing ring→through the joint, fixed to the
copper bar with M5 nut inside of the battery.
Battery communication cable connection sequence:
the RJ45 connector of the
communication cables shall go through the waterproof cap → through the sealing ring
→through the joint and inserted in to the COM port inside of the battery.
HV50056 & Battery communication cable connection sequence:
the RJ45 connec-
tor on one side shall go through the waterproof connector inserted into the COM port
inside the battery which is nearest to HV900112. The RJ45 connector on the other side
shall go through the waterproof cover inserted into the LMU port inside the HV50056.
HV50056 & Battery power cable connection sequence:
one side terminal shall go
through the waterproof cap→through the sealing ring→through the joint of the battery, fixed to
the copper bar with M5 nut inside of the battery; The plug connector on the other side shall be
connected to the plug port of the HV50056 with the corresponding color. When a snap sound is
heard, the connection is correct.
Terminal Resistance
INSTALLATION
INSTALLATION
17
18