5.0 SENSORS VERSION
After a short initial test, marked by alternate blinking of the Leds and by two short buzzer rings, the device
is ready awaiting for commands for the management of a 24Vdc motor for opening and closing a window.
The motor is controlled at the opening and closing depending on the condition of the AP and CH inputs or
the remote controller keys.
The opening of the motor stops in about 90 seconds; the closing stops when the IFC limit switch indicates
the closed window status or after about 90 seconds. The KFC relay replicates the IFC input's status.
If the device detects a wind speed greater then the threshold or the rain sensor is active the device goes in
the alarm state closing the window. When the alarm condition is removed the device exit the alarm state
after 8 minutes going into normal operation.
Table 3: Actions Thresolds
DESCRIPTION
Conn. M2:
4,5,6 KALL
Buzzer
Green LED
Red LED
Wind alarm
Active
OFF
OFF
FLASH 1
Rain Alarm
Active
OFF
OFF
SLOW
Normal operation
Resting
OFF
ON
OFF
SW1
Wind threshold
8
7
OFF
OFF
> 5 km/h
OFF
ON
> 15 km/h
ON
OFF
> 25 km/h
ON
ON
> 35 km/h
Table 2: Dip-switch SW1 settings
SW1
Alarm time-out
6
OFF
Fixed, 8 minutes
ON
After 10 seconds
the commands are
enabled
SW1
Remote controller
Keys
5
OFF
No action
ON
The OPEN and
CLOSE commands
reverse
The device communicates outdoors it's status with two Leds: red and green, the buzzer and the KAL relay
as summarized in
Table 3
and described in
picture 1
.