Allied Solar Pty Ltd
14
P-MAN-01-1a_Rev B
Installation, Operation and Maintenance Manual – AS-2560
4.6
Specifications
Following is a list of specifications and settings for the Allied Solar AS-2560. These settings should
already be programmed into the unit.
General
Output power (maximum continuous)
3000
W
Voltage
220 – 240
V AC
Frequency
50
Hz
Current (maximum continuous)
13
A
Phases
1
Ambient temperature range
-5 to 45
C
Altitude
0 – 3000
m
Batteries
Calb CA100
Capacity
100
Ah
Nominal Voltage
25.6
V
Capacity (100%)
2.56
kWh
Capacity (100%)
9.22
MJ
Capacity (working range 95%)
2.43
kWh
Capacity (working range 95%)
8.75
MJ
Fully charged Voltage
27.8
V
Fully discharged Voltage
21.0
V
Working temperature range
0 to 45
Deg C
Solar Panels
Recommend - Risen 370W
Number of inputs
1
Number of strings per input
Max 2
Number of panels per string
Min 2 – Max 3*
Voc per string
Min 47– Max 150
V
Charge Controller
e-Smart3
Maximum charging current
60
A
Battery type
“User”
Maximum Voc (string)
150
V
Load type
On
System Voltage
24
V
Inverter
Voltage
220 – 240
V AC
Power (Peak)
6000
W
Power (Continuous)
3000
W
Battery Meter Settings
CAP
100
Ah
Full
27.55
V
Zero
21.1
V
Drift
Do not change
mA
Back-up power supply (Generator)
Voltage
220 – 240
V AC