507277-02
Page 38 of 52
Issue 1621
Gas Pressure Adjustment
Gas Flow (Approximate)
NOTE:
To obtain accurate reading, shut off all other gas
appliances connected to meter.
Furnace should operate at least 5 minutes before checking
gas flow. Determine time in seconds for
two
revolutions of
gas through the meter. (Two revolutions assures a more
accurate time.)
Divide by two
and compare to time in
Table 11. If manifold pressure matches Table 12 and rate
is incorrect, check gas orifices for proper size and restriction.
Remove temporary gas meter if installed.
Supply Pressure Measurement
A threaded plug on the inlet side of the gas valve provides
access to the supply pressure tap. Remove the threaded
plug, install a field-provided barbed fitting and connect
a manometer to measure supply pressure. Replace the
threaded plug after measurements have been taken.
Manifold Pressure Measurement
1. Remove the threaded plug from the outlet side of the gas
valve and install a field provided barbed fitting. Connect
to a manometer to measure manifold pressure.
2. Start unit and allow 5 minutes for unit to reach steady
state.
Proper Combustion
Furnace should operate minimum 15 minutes with correct
manifold pressure and gas flow rate before checking
combustion. Take combustion sample beyond the flue outlet
and compare to the tables below.
The maximum carbon
monoxide reading should not exceed 100 ppm.
High Altitude Information
NOTE:
In Canada, certification for installations at elevations
over 4500 feet (1372 m) is the jurisdiction of local authorities.
Units may be installed at altitudes up to 10,000 ft. above
sea level. See table 12 for de-rate manifold values. Units
installed at altitude of 7501 - 10,000 feet require an orifice
change. Units installed at altitudes of 4501 - 10,000 feet
(1373 to 3048 m) require a pressure switch change which
can be ordered separately. Table 14 lists conversion kit and
pressure switch requirements at varying altitudes.
The combustion air pressure switch is factory-set and
requires no adjustment.
Table 12
Table 11
GAS METER CLOCKING CHART
Unit
Seconds for One Revolution
Natural
LP
1 cu ft
Dial
2 cu ft
Dial
1 cu ft
Dial
2 cu ft
Dial
−045
80
160
200
400
−070
55
110
136
272
−090
41
82
102
204
−110
33
66
82
164
−135
27
54
68
136
Natural−1000 btu/cu ft LP−2500 btu/cu ft
3. While waiting for the unit to stabilize, observe the flame.
Flame should be stable and should not lift from burner.
Natural gas should burn blue.
4. After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in
Table 12.
NOTE:
Shut unit off and remove manometer as soon as an
accurate reading has been obtained. Take care to remove
barbed fitting and replace threaded plug.
Page 1
10/13
*2P1013*
507280-01
*P507280-01*
TABLE 1
Manifold and Supply Line Pressure 0-10,000ft.
Unit
Gas
Manifold Pressure in. wg.
Supply Line Pressure
in. w.g.
0 - 10000 ft.
0-4500 ft.
4501-5500 ft.
5501-6500 ft.
6501 - 7500ft.
7501 - 10000ft.
All Sizes
Natural
3.5
3.3
3.2
3.1
3.5
4.5
13.0
LP/propane
10.0
9.4
9.1
8.9
10.0
11.0
13.0
NOTE -
A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion
procedure.
TABLE 2
Manifold and Supply Line Pressure 0-10,000ft.
Unit
Gas
Manifold Pressure in. wg.
Supply Line
Pressure
in. w.g.
0 - 10000 ft.
0-4500 ft.
4501-5500 ft.
5501-6500 ft.
6501 - 7500ft.
7501 - 10000ft.
Low
Fire
High
Fire
Low
Fire
High
Fire
Low
Fire
High
Fire
Low
Fire
High
Fire
Low
Fire
High
Fire
Min
Max
All
Sizes
Natural
1.7
3.5
1.6
3.3
1.5
3.2
1.5
3.1
1.7
3.5
4.5
13.0
LP/propane
4.9
10.0
4.6
9.4
4.4
9.1
4.3
8.9
4.9
10.0
11.0
13.0
NOTE -
A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion
procedure.
Table 13
Unit
CO
2
% for Nat
CO
2
% for L.P.
All
7.2 - 7.9
8.6 - 9.3
The maximum carbon monoxide reading should not exceed 100 ppm.
Summary of Contents for 95G1DFE
Page 29: ...507277 02 Page 29 of 52 Issue 1621 Figure 43 Trap Drain Assembly Using 1 2 PVC or 3 4 PVC ...
Page 35: ...507277 02 Page 35 of 52 Issue 1621 Typical Wiring Diagram Figure 50 For A95DF1E 95G1DFE ...
Page 46: ...507277 02 Page 46 of 52 Issue 1621 Troubleshooting Heating Sequence of Operation ...
Page 47: ...507277 02 Page 47 of 52 Issue 1621 Troubleshooting Heating Sequence of Operation continued ...
Page 48: ...507277 02 Page 48 of 52 Issue 1621 Troubleshooting Cooling Sequence of Operation ...
Page 49: ...507277 02 Page 49 of 52 Issue 1621 Troubleshooting Continuous Fan Sequence of Operation ...