ACCESSORIES
System Accessory
Where Used
Kit Number
Purpose
Compressor Low Ambient Kit
All models
45F08
Enables cooling demand down to 30 °F. Will require freeze stat, CC heater and TXV
Hard Start
18
10J42
Scroll compressors usually do not require hard start; maybe needed for utility brown-
out or low voltage areas
24 thru 60
88M91
Crankcase Heater
18, 24, 30, 36
93M04
Prevents liquid migration to compressor in cold weather
42, 48, 60
93M05
Sound Cover
All models
69J03
Lowers compressor sound level
Short Cycle Protector
All models
47J27
Delays compressor start 5-7 minutes to prevent short cycling
Loss of Charge Kit
All models
84M23
Protects the compressor if refrigerant charge is too low
TXV Kit
18, 24, 30, 36
A4TXV01
TXVs provide superior refrigerant flow control, comfort and efficiency compared to
pistons
42, 48, 60
A4TXV02
Freezestat
3/8” tubing
93G35
Protects the compressor at low suction pressure conditions
5/8” tubing
50A93
Blower Time Delay Relay
All models
58M81
Improves system efficiency and comfort