
508226-01
Issue 2135
Page 13 of 38
When outdoor unit is connected to factory-approved indoor
unit, outdoor unit contains system refrigerant charge for
operation with matching indoor unit when connected by 15
ft. of field-supplied tubing. For proper unit operation, check
refrigerant charge using charging information located on
control box cover.
Outdoor Section
Zoning ordinances may govern the minimum distance the
condensing unit can be installed from the property line.
Install on a Solid, Level Mounting Pad
The outdoor section is to be installed on a solid foundation.
This foundation should extend a minimum of 2” (inches)
beyond the sides of the outdoor section. To reduce the
possibility of noise transmission, the foundation slab
should NOT be in contact with or be an integral part of the
building foundation. See Figure 2.
If conditions or local codes require the unit be attached to
pad or mounting frame, tie down bolts should be used and
secured to unit base pan.
Discharge Air
Mounting Slab
Ground Level
Building
Structure
Mounting slab must slope slightly away from
building, not to exceed 1/4” per foot.
Figure 2. Slab Mounting
Elevate Unit
Accumulation of water and ice in base pan may cause
equipment damage.
CAUTION
Elevate unit per local climate and code requirements to
provide clearance above estimated snowfall level and
ensure adequate drainage of unit. Use snow stand in areas
where prolonged freezing temperatures are encountered.
If conditions or local codes require the unit be attached to
pad or mounting frame, tie down bolts should be used and
fastened through knockouts provided in unit base pan.
Refrigerant Metering Device - Indoor Coil
For correct metering device, refer to chart below.
Outdoor Model
Orifice
Size
Indoor
Expansion
Device
4AC13*18P-3,4,5,6A
0.051
A4TXV01
4AC13*18P-7,8,9,10,11A
0.053
A4TXV01
4AC13*24P
0.057
A4TXV01
4AC13*30P-3,5,6,8,9A
0.065
A4TXV01
4AC13*30P-7,10A
0.063
A4TXV01
4AC13*36P-3A
0.073
A4TXV01
4AC13*36P-4,5A
0.070
A4TXV01
4AC13*36P-7,8,9,10A
0.072
A4TXV01
4AC13*42P-3,4,5,6A
0.076
A4TXV02
4AC13*42P-7,8,9,10A
0.074
A4TXV02
4AC13*48P
0.082
A4TXV02
4AC13*60P-3A
0.093
A4TXV02
4AC13*60P-4,5,7,8,9,10,11A
0.090
A4TXV02
Table 1.
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
who have jurisdiction before installation.
Installation
NOTE:
In some cases, noise in the living area has been
traced to gas pulsations from improper installation of
equipment.
•
Locate unit away from windows, patios, decks, etc.
where unit operation sounds may disturb customer.
•
Leave some slack between structure and unit to
absorb vibration.
•
Place a sound-absorbing material, such as Isomode,
under the unit if it will be installed in a location or
position that will transmit sound or vibration to the
living area or adjacent buildings.
•
In heavy snow areas, do not locate the unit where
drifting snow will occur. The unit base should be
elevated above the depth of average snows.
NOTE:
Elevation of the unit may be accomplished
by constructing a frame using suitable materials. If a
support frame is constructed, it must not block drain
holes in unit base.
•
When installed in areas where low ambient
temperatures exist, locate unit so winter prevailing
winds do not blow directly into outdoor coil.
•
Locate unit away from overhanging roof lines which
would allow water or ice to drop on, or in front of, coil
or into unit.
Summary of Contents for 4AC13B
Page 31: ...508226 01 Issue 2135 Page 31 of 38 Figure 13 Wiring Diagram Wiring Diagram ...
Page 35: ...508226 01 Issue 2135 Page 35 of 38 Charge Labels Figure 14 4AC13 10 11 ...
Page 36: ...508226 01 Issue 2135 Page 36 of 38 Figure 15 4AC13 7 8 ...
Page 37: ...508226 01 Issue 2135 Page 37 of 38 Figure 16 4AC13 3 4 5 6 ...