Allied 4AC13B Service Manual Download Page 13

508226-01

Issue 2135

Page 13 of 38

When outdoor unit is connected to factory-approved indoor 

unit,  outdoor  unit  contains  system  refrigerant  charge  for 

operation with matching indoor unit when connected by 15 

ft. of field-supplied tubing. For proper unit operation, check 

refrigerant  charge  using  charging  information  located  on 

control box cover.

Outdoor Section

Zoning ordinances may govern the minimum distance the 

condensing unit can be installed from the property line. 

Install on a Solid, Level Mounting Pad

The outdoor section is to be installed on a solid foundation. 

This foundation should extend a minimum of 2” (inches) 

beyond  the  sides  of  the  outdoor  section.  To  reduce  the 

possibility  of  noise  transmission,  the  foundation  slab 

should NOT be in contact with or be an integral part of the 

building foundation. See Figure 2.

If conditions or local codes require the unit be attached to 

pad or mounting frame, tie down bolts should be used and 

secured to unit base pan.

Discharge Air

Mounting Slab

Ground Level

Building

Structure

Mounting slab must slope slightly away from 

building, not to exceed 1/4” per foot.

Figure 2. Slab Mounting

Elevate Unit

Accumulation of water and ice in base pan may cause 

equipment damage.

 CAUTION

Elevate  unit  per  local  climate  and  code  requirements  to 

provide  clearance  above  estimated  snowfall  level  and 

ensure adequate drainage of unit. Use snow stand in areas 

where prolonged freezing temperatures are encountered.

If conditions or local codes require the unit be attached to 

pad or mounting frame, tie down bolts should be used and 

fastened through knockouts provided in unit base pan.

Refrigerant Metering Device - Indoor Coil

For correct metering device, refer to chart below.

Outdoor Model

Orifice 

Size

Indoor 

Expansion 

Device

4AC13*18P-3,4,5,6A

0.051

A4TXV01

4AC13*18P-7,8,9,10,11A

0.053

A4TXV01

4AC13*24P

0.057

A4TXV01

4AC13*30P-3,5,6,8,9A

0.065

A4TXV01

4AC13*30P-7,10A

0.063

A4TXV01

4AC13*36P-3A

0.073

A4TXV01

4AC13*36P-4,5A

0.070

A4TXV01

4AC13*36P-7,8,9,10A

0.072

A4TXV01

4AC13*42P-3,4,5,6A

0.076

A4TXV02

4AC13*42P-7,8,9,10A

0.074

A4TXV02

4AC13*48P

0.082

A4TXV02

4AC13*60P-3A

0.093

A4TXV02

4AC13*60P-4,5,7,8,9,10,11A

0.090

A4TXV02

Table 1.  

These instructions are intended as a general guide and do 

not supersede local codes in any way. Consult authorities 

who have jurisdiction before installation.

Installation

NOTE: 

In some cases, noise in the living area has been 

traced to gas pulsations from improper installation of 

equipment.

• 

Locate  unit  away  from  windows,  patios,  decks,  etc. 

where unit operation sounds may disturb customer.

• 

Leave  some  slack  between  structure  and  unit  to 

absorb vibration.

• 

Place a sound-absorbing material, such as Isomode, 

under  the  unit  if  it  will  be  installed  in  a  location  or 

position  that  will  transmit  sound  or  vibration  to  the 

living area or adjacent buildings.

• 

In  heavy  snow  areas,  do  not  locate  the  unit  where 

drifting  snow  will  occur.  The  unit  base  should  be 

elevated above the depth of average snows.

NOTE: 

Elevation of the unit may be accomplished 

by constructing a frame using suitable materials. If a 

support frame is constructed, it must not block drain 

holes in unit base.

• 

When  installed  in  areas  where  low  ambient 

temperatures  exist,  locate  unit  so  winter  prevailing 

winds do not blow directly into outdoor coil.

• 

Locate  unit  away  from  overhanging  roof  lines  which 

would allow water or ice to drop on, or in front of, coil 

or into unit.

Summary of Contents for 4AC13B

Page 1: ...er be ignored When you see this symbol on labels or in manuals be alert to the potential for personal injury or death Electric shock hazard Can cause injury or death Before attempting to perform any service or maintenance turn the electrical power to unit OFF at disconnect switch es Unit may have multiple power supplies WARNING As with any mechanical equipment contact with sharp sheet metal edges ...

Page 2: ...45 21 2 90 1 7 1 4 825 4AC13 42P 11 208 230 60 1 197 253 25 7 40 19 2 124 1 7 1 4 825 4AC13 48P 10 208 230 60 1 197 253 31 9 50 24 2 100 1 7 1 4 825 4AC13 48P 11 208 230 60 1 197 253 31 9 50 24 2 100 1 7 1 4 825 4AC13 60P 10 208 230 60 1 197 253 34 7 60 26 4 125 1 7 1 4 825 4AC13 60P 11 208 230 60 1 197 253 34 7 60 26 4 125 1 7 1 4 825 Overcurrent protection device UNIT DIMENSIONS IN Model No Dime...

Page 3: ...o 30 F Will require freeze stat CC heater and TXV Compressor Short Cycle Protector All models 47J27 Delays compressor start 5 7 minutes to prevent short cycling Hard Start 18 10J42 Scroll compressors usually do not require hard start maybe needed for utility brown out or low voltage areas 24 thru 60 88M91 Crankcase Heater 18 24 30 36 93M04 Prevents liquid migration to compressor in cold weather 42...

Page 4: ... H4TXV02 Note 1 Required to achieve AHRI rating If NA Not Applicable is in the piston column then TXV is required 2 Use 3 8 if over 24 feet of line set 3 Use 3 4 if over 24 feet of line set 4 Use 1 1 8 if over 24 feet of line set Adapter provided with OD unit 5 Use 7 8 if over 24 feet of line set 6 Charged for 15 ft of line set 7 DTC Designated Tested Combination COOLING PERFORMANCE WITH DTC1 Outd...

Page 5: ...9 50 24 1 100 1 7 1 4 825 124 4AC13 60P 7 8 208 230 60 1 197 253 29 4 50 22 1 120 1 7 1 4 825 144 Overcurrent protection device Factory charge adequate for 15 feet of line set Adjust per installation instructions UNIT DIMENSIONS IN SOUND RATINGS Model No Dimensions Shipping Weight lbs Sound Ratings dBA A Width B Depth C Height Louvered 4AC13 18P 7 8 24 25 24 25 25 136 74 4AC13 24P 7 8 24 25 24 25 ...

Page 6: ...tion to compressor in cold weather 42 48 60 93M05 Sound Cover All models 69J03 Lowers compressor sound level Short Cycle Protector All models 47J27 Delays compressor start 5 7 minutes to prevent short cycling Loss of Charge Kit All models 84M23 Protects the compressor if refrigerant charge is too low TXV Kit 18 24 30 36 A4TXV01 TXVs provide superior refrigerant flow control comfort and efficiency ...

Page 7: ...97 253 29 4 50 22 1 120 1 7 1 4 825 160 Overcurrent protection device Factory charge adequate for 15 feet of line set Adjust per installation instructions UNIT DIMENSIONS IN SOUND RATINGS Model No Dimensions Shipping Weight lbs Sound Ratings dBA A Width B Depth C Height Wire Guard Louvered 4AC13 18P 5 24 25 24 25 25 130 138 76 4AC13 24P 5 24 25 24 25 25 132 140 76 4AC13 30P 5 24 25 24 25 29 142 15...

Page 8: ...tion to compressor in cold weather 42 48 60 93M05 Sound Cover All models 69J03 Lowers compressor sound level Short Cycle Protector All models 47J27 Delays compressor start 5 7 minutes to prevent short cycling Loss of Charge Kit All models 84M23 Protects the compressor if refrigerant charge is too low TXV Kit 18 24 30 36 A4TXV01 TXVs provide superior refrigerant flow control comfort and efficiency ...

Page 9: ... 6 60 26 3 120 1 7 1 4 825 160 Overcurrent protection device Factory charge adequate for 15 feet of line set Adjust per installation instructions UNIT DIMENSIONS IN SOUND RATINGS Model No Dimensions Shipping Weight lbs Sound Ratings dBA A Width B Depth C Height Wire Guard Louvered 4AC13 18P 5 24 25 24 25 24 50 130 138 76 4AC13 24P 5 24 25 24 25 24 50 132 140 76 4AC13 30P 5 24 25 24 25 28 50 142 15...

Page 10: ...tion to compressor in cold weather 42 48 60 93M05 Sound Cover All models 69J03 Lowers compressor sound level Short Cycle Protector All models 47J27 Delays compressor start 5 7 minutes to prevent short cycling Loss of Charge Kit All models 84M23 Protects the compressor if refrigerant charge is too low TXV Kit 18 24 30 36 A4TXV01 TXVs provide superior refrigerant flow control comfort and efficiency ...

Page 11: ... Issue 2135 Page 11 of 38 FAN BLADE SPECS 4AC13 3 thru 11 Fan Blade Dia of Blades Pitch Part 18 18 3 27 98M18 24 18 3 27 98M18 30 18 4 27 98M19 36 18 4 27 98M19 42 22 4 32 30W24 48 22 4 32 30W24 60 22 4 32 30W24 ...

Page 12: ...UTDOOR COIL DISCHARGE LINE HIGH PRESSURE SWITCH COMPRESSOR GROUND LUG CONTACTOR CONTROL DUAL RUN CAPACITOR CONTROL WIRE LOOP CUTOUT FOR HIGH VOLTAGE CONDUIT NOTE Plumbing layout and compressor type may vary between model sizes CRANKCASE HEATER THERMOSTAT CRANKCASE HEATER THERMAL SWITCH Figure 1 Typical Parts Arranegment ...

Page 13: ...d in unit base pan Refrigerant Metering Device Indoor Coil For correct metering device refer to chart below Outdoor Model Orifice Size Indoor Expansion Device 4AC13 18P 3 4 5 6A 0 051 A4TXV01 4AC13 18P 7 8 9 10 11A 0 053 A4TXV01 4AC13 24P 0 057 A4TXV01 4AC13 30P 3 5 6 8 9A 0 065 A4TXV01 4AC13 30P 7 10A 0 063 A4TXV01 4AC13 36P 3A 0 073 A4TXV01 4AC13 36P 4 5A 0 070 A4TXV01 4AC13 36P 7 8 9 10A 0 072 ...

Page 14: ...codes for rooftop applications If unit cannot be mounted away from prevailing winds a wind barrier should be constructed Due to variation in installation applications size and locate barrier according to the best judgment of the installer Torque Requirements When servicing or repairing heating ventilating and air conditioning components ensure the fasteners are appropriately tightened Table 3 list...

Page 15: ...ch 2 Connect gauge to the service port 3 When testing is completed replace service port cap Tighten finger tight then an additional 1 6 turn To Open Liquid or Suction Line Service Valve 1 Remove stem cap with an adjustable wrench 2 Use service wrench with a hex head extension to back the stem out counterclockwise as far as it will go Use a 3 16 hex head extension for liquid line service valves and...

Page 16: ...ise at service valve CAUTION Refrigeration Piping Use only refrigerant grade copper tubes Split systems may be installed with up to 50 feet of line set no more than 20 feet vertical without special consideration see long line set guidelines Ensure that vapor and liquid tube diameters are appropriate to capacity of unit Run refrigerant tubes as directly as possible by avoiding unnecessary turns and...

Page 17: ... THEN STRAP THE LIQUID LINE TO THE VAPOR LINE FLOOR JOIST OR ROOF RAFTER REFRIGERANT LINE SET INSTALLING HORIZONTAL RUNS NOTE Similar installation practices should be used if line set is to be installed on exterior of outside wall PVC PIPE FIBERGLASS INSULATION CAULK OUTSIDE WALL VAPOR LINE WRAPPED WITH ARMAFLEX LIQUID LINE OUTSIDE WALL LIQUID LINE VAPOR LINE WOOD BLOCK BETWEEN STUDS STRAP WOOD BL...

Page 18: ...iquid line orifice housing SENSING LINE TWO PIECE PATCH PLATE UNCASED COIL ONLY VAPOR LINE DISTRIBUTOR ASSEMBLY DISTRIBUTOR TUBES LIQUID LINE MALE EQUALIZER LINE FITTING EQUALIZER LINE EXPANSION VALVE TEFLON RING STUB END TEFLON RING SENSING BULB LIQUID LINE ORIFICE HOUSING LIQUID LINE ASSEMBLY WITH BRASS NUT Figure 6 Remove Existing Expansion Valve uncased coil shown Flushing Line Sets If the uni...

Page 19: ...gauges and equipment as shown in Figure 7 2 Set the recovery machine for liquid recovery and start the recovery machine Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line set and indoor unit coil 3 Position the cylinder of clean R 410A for delivery of liquid refrigerant and open its valve to allow liquid refrigerant to flow into the system through ...

Page 20: ...wn Sensing bulb insulation is required if mounted external to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR ASSEMBLY 3 Install one of the provided Teflon rings around the stubbed end of the check expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil...

Page 21: ...ssure side to liquid line service valve service port B Connect gauge set center port to bottle of nitrogen with regulator C Remove core from valve in vapor line service port to allow nitrogen to escape NITROGEN HIGH LOW USE REGULATOR TO FLOW NITROGEN AT 1 TO 2 PSIG B A C WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the l...

Page 22: ...VES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated cloths around service valve bodies and copper tube stubs Use additionalwater saturated cloths underneath the valve body to protect the base paint 4 FLOW NITROGEN Flow regulated nitrogen at 1 to 2 psig through the refrigeration gauge set int...

Page 23: ...he valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector F After the line set has been connected to the indoor and outdoor units check the line set connections and indoor unit for leaks Use the fo...

Page 24: ...uid refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following Close manifold gauge valves Shut off HFC 410A cylinder Reinstall service valve cores by removing manifold hose from service valve Quickly install cores with core tool while maintaining a positive system pressure Replace stem caps and finger tighten them t...

Page 25: ...cess high voltage field wiring should be trimmed or secured away from the low voltage field wiring 2 High voltage power connections to 3 phase models is made to Pig Tail leads with field supplied splice connectors 3 Ground unit at unit disconnect switch or to an earth ground To facilitate conduit a hole is in the bottom of the control box Connect conduit to the control box using a proper conduit f...

Page 26: ...508226 01 Issue 2135 Page 26 of 38 HIGH PRESSURE SWITCH S4 LIQUID LINE CRANKCASE THERMOSTAT S40 CRANKCASE HEATER HR1 Figure 9 Typical Factory Wiring Diagram Copeland Compressor ...

Page 27: ...01 Issue 2135 Page 27 of 38 CRANKCASE HEATER HR1 HIGH PRESSURE SWITCH S4 LIQUID LINE CRANKCASE THERMOSTAT S40 THERMAL PROTECTION SWITCH S5 OR S173 Figure 10 Typical Factory Wiring Diagram Interlink Compressor ...

Page 28: ... the indoor evaporator and outdoor temperatures above 65 F charge using the superheat method and table provided on the unit access panel For systems using a TXV on the indoor evaporator and outdoor temperature above 60 F charge in Sequence of Operation NOTE The thermostat used may be electromechanical or electronic NOTE Transformer in indoor unit supplies power 24 VAC to the thermostat and outdoor...

Page 29: ...rushed from the condenser coils Use a soft bristle brush with light pressure only DO NOT damage or bend condenser coil fins Damaged or bent fins may affect unit operation Figure 11 Removing Louvers Remove two screws at top panel to remove louvers for coil access SHARP OBJECT HAZARD Condenser coils have sharp edges Wear adequate body protection on body extremities e g gloves FAILURE TO FOLLOW THIS ...

Page 30: ...windy conditions that may cause panels to be blown around and battered WARNING REMOVAL STEP 1 INSERT PANEL UNDER UNIT TOP CAP LIP AND LIFT SLIGHTLY TO CLEAR SIDE LIP OF PANEL FROM BASE STEP 2 PANEL INSTALLATION TO REMOVE PANEL REMOVE MOUNTING SCREWS SECURING PANEL TO THE UNIT SLIGHTLY LIFT PANEL IN ORDER TO CLEAR SIDE LIPS OF PANEL FROM BASE OF UNIT STEP 3 TILT PANEL OUT SLIGHTLY AND PULL DOWNWARD...

Page 31: ...508226 01 Issue 2135 Page 31 of 38 Figure 13 Wiring Diagram Wiring Diagram ...

Page 32: ...UID PHASE CONNECTIONS FOR TESTING AND CHARGING GAUGE SET A C D LOW HIGH B SUCTION LINE SERVICE PORT CONNECTION Servicing Units Void of Charge If the outdoor unit is void of refrigerant clean the system using the procedure described below 1 Leak check system using procedure outlined on Page 23 2 Evacuate the system using procedure outlined on Page 23 3 Use nitrogen to break the vacuum and install a...

Page 33: ...59 60 61 62 63 64 65 66 67 68 69 70 Temperature of air entering indoor coil ºF INDOOR COIL DRY BULB DRY BULB WET BULB B TDrop 19º A Dry bulb Wet bulb ºF A 72º B 64º C 53º air flow air flow All temperatures are expressed in ºF 1 Determine the desired DT Measure entering air temperature using dry bulb A and wet bulb B DT is the intersecting value of A and B in the table see triangle 2 Find temperatu...

Page 34: ...0 10 23 3 36 8 90 32 2 274 0 5 20 6 42 5 95 35 0 295 0 0 17 8 48 6 100 37 8 317 0 5 15 0 55 2 105 40 6 340 0 10 12 2 62 3 110 43 3 365 0 15 9 4 70 0 115 46 1 391 0 20 6 7 78 3 120 48 9 418 0 25 3 9 87 3 125 51 7 446 0 30 1 1 96 8 130 54 4 476 0 35 1 7 107 0 135 57 2 507 0 40 4 4 118 0 140 60 0 539 0 45 7 2 130 0 145 62 8 573 0 50 10 0 142 0 150 65 6 608 0 55 12 8 155 0 Table 6 HFC 410A Temperature...

Page 35: ...508226 01 Issue 2135 Page 35 of 38 Charge Labels Figure 14 4AC13 10 11 ...

Page 36: ...508226 01 Issue 2135 Page 36 of 38 Figure 15 4AC13 7 8 ...

Page 37: ...508226 01 Issue 2135 Page 37 of 38 Figure 16 4AC13 3 4 5 6 ...

Page 38: ...________________________________________________ Rated LoadAmpacity ________________ Compressor _______________________ Outdoor Fan ________________________ Maximum Fuse or Circuit Breaker _______________________________________________________________________________ Electrical Connections Tight Indoor Filter Clean Supply Voltage Unit Off _______________ Indoor Blower RPM _________________ S P Dr...

Reviews: