Chapter 3: Installing the Power Supply
58
Wiring the Power Alert DC_OK Connector
For background information, refer to “Power Alert DC_OK Connectors” on
page 27. This procedure requires the following:
Two DC_OK connector wires. Refer to Table 10 on page 46 for the
specifications.
Cross-head screwdriver (not provided).
Wire insulator stripper (not provided).
Alert device (not provided).
To wire the Power Alert DC_OK connector, perform the following
procedure:
1. Prepare adequate lengths of cables by stripping 8mm of insulation
from the ends.
2. Loosen the two DC_OK connector screws on the front panel and insert
the wires into the connectors on the top panel. Refer to Figure 16.
Figure 16. Wiring the DC_OK Connector
3. Tighten the screws to secure the wires.
4. Visually inspect the wires for exposed wires and loose strands. Refer
5. Connect the wires to the alert device.