506892-01
Page 45 of 64
Issue 1251
At the beginning of each heating season, a qualified
technician should check the system as follows:
Blower
Check the blower wheel for debris and clean if necessary.
The blower motors are prelubricated for extended bearing
life. No further lubrication is needed.
Flue And Chimney
1.
Check flue pipe, chimney and all connections for
tightness and to make sure there is no blockage.
2.
Check unit for proper draft.
Electrical
1.
Check all wiring for loose connections.
2.
Check for the correct voltage at the furnace (furnace
operating). Correct voltage is 120VAC ± 10%.
3.
Check amp-draw on the blower motor with blower panel
in place.
Unit Nameplate________Actual ________ _
SERVICE
Filters
All filters are installed external to the unit. Filters should be
inspected monthly. Clean or replace the filters when
necessary to ensure that the furnace operates properly.
Replacement filters must be rated for high velocity airflow.
Table 3 lists recommended filter sizes.
WARNING
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could result in
dangerous operation, serious injury, death or property
damage.
Improper servicing could result in dangerous operation,
serious injury, death, or property damage.
Before servicing, disconnect all electrlcal power to
furnace.
When servicing controls, label all wires prior to
disconnecting. Take care to reconnect wires correctly.
Verify proper operation after servicing.
WARNING
The blower access panel must be securely in place
when the blower and burners are operating. Gas fumes,
which could contain carbon monoxide, can be drawn
into living space resulting in personal injury or death.
Summary of Contents for A80DS2V
Page 3: ...506892 01 Page 3 of 64 Issue 1251 EXPANDED VIEW Figure 1...
Page 24: ...506892 01 Page 24 of 64 Issue 1251 Figure 22...
Page 30: ...506892 01 Page 30 of 64 Issue 1251 Figure 24 A80DS2V Schematic Wiring Diagram...
Page 31: ...506892 01 Page 31 of 64 Issue 1251 Typical A80DS2V Field Wiring Diagram Figure 25...
Page 32: ...506892 01 Page 32 of 64 Issue 1251 Integrated Control Figure 26...
Page 50: ...506892 01 Page 50 of 64 Issue 1251 Integrated Control Diagnostic Codes...
Page 51: ...506892 01 Page 51 of 64 Issue 1251 Integrated Control Diagnostic Codes continued...
Page 52: ...506892 01 Page 52 of 64 Issue 1251 Integrated Control Diagnostic Codes continued...
Page 53: ...506892 01 Page 53 of 64 Issue 1251 Integrated Control Diagnostic Codes continued...
Page 54: ...506892 01 Page 54 of 64 Issue 1251 Integrated Control Diagnostic Codes continued...
Page 55: ...506892 01 Page 55 of 64 Issue 1251 Program Unit Capacity Size Mode...
Page 56: ...506892 01 Page 56 of 64 Issue 1251 Troubleshooting Heating Sequence of Operation...
Page 57: ...506892 01 Page 57 of 64 Issue 1251 Troubleshooting Heat Sequence of Operation continued...
Page 58: ...506892 01 Page 58 of 64 Issue 1251 Troubleshooting Heat Sequence of Operation continued...
Page 59: ...506892 01 Page 59 of 64 Issue 1251 Troubleshooting Heat Sequence of Operation continued...
Page 60: ...506892 01 Page 60 of 64 Issue 1251 Troubleshooting Continuous Fan Sequence of Operation...
Page 61: ...506892 01 Page 61 of 64 Issue 1251 Start Up Performance Check List UNIT SET UP...
Page 62: ...506892 01 Page 62 of 64 Issue 1251 Start Up Performance Check List continued...