Location

Use the following guidelines to select a suitable location for
the unit.

1. Unit is designed for outdoor installation only.  Unit must

be installed so all electrical components are protected
from water.

2. Condenser coils must have an unlimited supply of air.

3. For ground level installation, use a level prefabricated

pad or use a level concrete slab.  Do not tie the slab to
the building foundation.

4. Maintain level within a tolerance of 1/4" maximum across

the entire length or width of the unit.

5. Do not locate the unit where the combustion air supply

will be exposed to any of the following substances:

Permanent wave solutions

Chlorinated waxes and cleaners

Chlorine-based swimming pool chemicals

Water softening chemicals

Deicing salts or chemicals

Carbon tetrachloride

Halogen-type refrigerants

Cleaning solvents (such as perchloroethylene)

Printing inks, paint removers, varnishes, etc.

Cements and glues

Antistatic fabric softeners for clothes dryers

Masonry acid washing materials

Chlorinated laundry products

Hydrochloric acid

Use of unit as a construction heater during any phase of
construction is not recommended.  Very low return air
temperatures, harmful vapors, and operation of the unit with
clogged or misplaced filters will damage the unit.  However,
if the installation and operating conditions specified below
are followed, use of this unit for heating of buildings or
structures under construction is permissible:

The vent hood must be installed per these installation
instructions.

A room thermostat must control the furnace.  The use
of fixed jumpers that will provide continuous heating is
not allowed.

The return air duct must be provided and sealed to the
unit.

Return air temperature must be maintained between
60°F (16°C) and 80°F (27°C).

Air filters must be installed in the system and must be
maintained during construction.

Air filters must be replaced upon construction completion.

The input rate and temperature rise must be set per the
unit rating plate.

100% outdoor air must be provided for combustion air
requirements during construction.  Installation of this unit
in its intended outdoor location will accomplish this.

The heat exchanger, components, duct system, air
filter(s), and evaporator coil must be thoroughly cleaned
following final construction cleanup.

Following the final cleaning, all furnace operating
conditions (including ignition, input rate, temperature
rise, and venting) must be verified according to these
instructions.

Exercise care when moving the unit.  Do not remove any
packaging until the unit is near the place of installation.  An
accessory lift kit can be purchased to aid in rigging (see
Figure 1).  Spreaders whose length exceed the largest
dimension across the unit 

must be used across the top of

the unit.  

Recommended spreader length:  3 ton and smaller

package units – 44", 3.5 ton and larger units – 54".

Units may also be moved or lifted with a forklift while still in
the factory-supplied packaging. 

 

The lengths of the forks

of the forklift must be a minimum of 42".

Using Accessory Lift Kit

Figure 1

To avoid possible
damage to unit
panels from lifting
clevis, place
packing material
between clevis
and panels before
lifting unit.

Spreaders

(Field Supplied)

Lifting Bracket

Accessory

Sheet Metal
Screw

Before lifting a unit, make sure that the weight is
distributed equally on the cables so that it will lift evenly.

 CAUTION

Summary of Contents for 4PGE

Page 1: ...it WARNING INSTALLATION AND MAINTENANCE INSTRUCTIONS 4PGE SG 13 15 Series Gas Heating Electric Cooling Package Unit Save these instructions for future reference The installation of the furnace wiring...

Page 2: ...er charge and airflow may reduce energy efficiency and shorten equipment life Inspection As soon as the unit is received it should be inspected for possible damage during transit If damage is evident...

Page 3: ...pers that will provide continuous heating is not allowed The return air duct must be provided and sealed to the unit Return air temperature must be maintained between 60 F 16 C and 80 F 27 C Air filte...

Page 4: ...above any door window or gravity air inlet into the building The vent system shall terminate at least 3 above any forced air inlet located within 10 The unit shall be installed in a manner such that s...

Page 5: ...nnected to the venting system being placed into operation while all other appliances connected to the common venting system are not in operation 1 Seal any unused openings in the common venting system...

Page 6: ...pening Filters Air filters are to be used with this heating cooling unit Filters are not factory supplied in the unit However a filter frame accessory is available from the manufacturer that allows fi...

Page 7: ...trap drip leg shall be installed as close as practical to the gas supply inlet of the unit LPG Propane Units Tanks and Piping Units are shipped equipped for natural gas but can be converted to LPG pro...

Page 8: ...wiring must be sized to carry minimum circuit ampacity marked on the unit Use copper conductors only Each unit must be wired with a separate branch circuit and be properly fused Thermostat The room t...

Page 9: ...Used WITHOUT ECONOMIZER L2 L1 POWER WIRING 208 230 1 60 75 C MIN WIRE POWER WIRING 24V CONTROL WIRING NEC CLASS 2 GROUND SCREW SINGLE PHASE L1 L2 L3 GROUND SCREW POWER WIRING 200 230 3 60 460 575 3 6...

Page 10: ...hould the supply pressure during standby exceed 13 w c nor should it be less than 5 w c for For Your Safety Read Before Lighting natural gas or 11 W C for propane gas with the burners in operation If...

Page 11: ...contained factory optimized refrigerant system and should require no adjustments when properly installed If however unit performance is questioned perform the following checks OPERATION The heating v...

Page 12: ...t work for air leaks as well as restrictions and blower speed settings If unit performance remains questionable remove charge evacuate to 500 Microns and weigh in refrigerant to name plate charge It i...

Page 13: ...loperateswhenahightemperature condition caused by inadequate airflow occurs This causes the ignition control to close the gas valve The circulation air blower continues to operate in this situation Pr...

Page 14: ...low tipping of the natural gas burner flame or long yellow tips on propane may be caused by lint accumulation or dirt inside the burner or burner ports at the air inlet between the burner and manifold...

Page 15: ...506488 01 Page 15 Issue 1008 Figure 11 Connection Diagram Single Phase PSC Motor...

Page 16: ...N 75 C WIRE WARNING ELECTRIC SHOCK HAZARD UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES HEAT ANTICIPATION SETTING 0 70 AMP LINE VOLTAGE FIELD INSTALLED SEE BLOWER SPEED CHART BLK S...

Reviews: