INSTALLATION

These instructions must be hung on or near the furnace
in a conspicuous place.

These units are single package air conditioners with gas heat
designed for outdoor installation on a rooftop or a slab.

The units are completely assembled.  All piping, refrigerant
charge, and electrical wiring are factory installed and tested.
The units require only electric power, gas piping, condensate
drain, and duct connections, plus assembly of the heating
vent hood at the point of installation.

If components are to be added to a unit to meet local codes,
they are to be installed at the dealer’s and/or customer’s
expense.

The size of unit for the proposed installation should be based
on heat loss/heat gain calculation made according to the
methods of Air Conditioning Contractors of America (ACCA).

These installation instructions are intended as a general
guide only, for use by an experienced, qualified
contractor.

These units are listed by UL:

For use as a forced air furnace with cooling unit.

For outdoor installation only.

For installation on combustible material.

For use with natural gas or propane gas.
(Conversion kit required for propane gas application.)

These units are not suitable for use with conventional
venting systems.

IMPORTANT: 

The 15 SEER models have been designed

and manufactured to meet ENERGY STAR criteria for energy
efficiency.  However, proper refrigerant charge and proper air
flow are critical to achieve rated capacity and efficiency.
Installation of this product should follow the manufacturer’s
refrigerant charging and air flow instructions. 

 Failure to

confirm proper charge and airflow may reduce energy
efficiency and shorten equipment life.

Inspection

As soon as the unit is received, it should be inspected for
possible damage during transit.  If damage is evident, the
extent of the damage should be noted on the carrier’s freight
bill.  A separate request for inspection by the carrier’s agent
should be made in writing.

SAFETY

The following is a list of safety rules and precautions that
must be followed when installing this furnace.

1. Use only with the type of gas approved for this furnace.

Refer to the furnace rating plate.

2. Install this furnace only in a location and position as

specified in the Location section on page 3 of these
instructions.

3. Adequate clearance must be provided around the vent

hood as specified in the Clearances section on page 4 of
these instructions.

4. Never test for gas leaks with an open flame.  Use a

commercially available soap solution made specifically
for the detection of leaks to check all connections, as
specified in Gas Supply and Piping beginning on page
6 of these instructions.

5. Always install furnace to operate within the furnace’s

intended temperature-rise range with a duct system which
has an external static pressure within the allowable range,
as specified in Temperature Rise on page 11 of these
instructions. See furnace rating plate.

6. The furnace is not recommended for use for temporary

heating of buildings or structures under construction unless
certain installation and operating conditions are adhered
to, as specified in the Location section on page 3 of these
instructions.

In the State of Massachusetts:

This product must be installed by a licensed Plumber
or Gas Fitter.  When flexible connectors are used, the
maximum length shall not exceed 36".  When lever-
type gas shutoffs are used, they shall be T-handle type.

  WARNING

Summary of Contents for 4PGE

Page 1: ...it WARNING INSTALLATION AND MAINTENANCE INSTRUCTIONS 4PGE SG 13 15 Series Gas Heating Electric Cooling Package Unit Save these instructions for future reference The installation of the furnace wiring...

Page 2: ...er charge and airflow may reduce energy efficiency and shorten equipment life Inspection As soon as the unit is received it should be inspected for possible damage during transit If damage is evident...

Page 3: ...pers that will provide continuous heating is not allowed The return air duct must be provided and sealed to the unit Return air temperature must be maintained between 60 F 16 C and 80 F 27 C Air filte...

Page 4: ...above any door window or gravity air inlet into the building The vent system shall terminate at least 3 above any forced air inlet located within 10 The unit shall be installed in a manner such that s...

Page 5: ...nnected to the venting system being placed into operation while all other appliances connected to the common venting system are not in operation 1 Seal any unused openings in the common venting system...

Page 6: ...pening Filters Air filters are to be used with this heating cooling unit Filters are not factory supplied in the unit However a filter frame accessory is available from the manufacturer that allows fi...

Page 7: ...trap drip leg shall be installed as close as practical to the gas supply inlet of the unit LPG Propane Units Tanks and Piping Units are shipped equipped for natural gas but can be converted to LPG pro...

Page 8: ...wiring must be sized to carry minimum circuit ampacity marked on the unit Use copper conductors only Each unit must be wired with a separate branch circuit and be properly fused Thermostat The room t...

Page 9: ...Used WITHOUT ECONOMIZER L2 L1 POWER WIRING 208 230 1 60 75 C MIN WIRE POWER WIRING 24V CONTROL WIRING NEC CLASS 2 GROUND SCREW SINGLE PHASE L1 L2 L3 GROUND SCREW POWER WIRING 200 230 3 60 460 575 3 6...

Page 10: ...hould the supply pressure during standby exceed 13 w c nor should it be less than 5 w c for For Your Safety Read Before Lighting natural gas or 11 W C for propane gas with the burners in operation If...

Page 11: ...contained factory optimized refrigerant system and should require no adjustments when properly installed If however unit performance is questioned perform the following checks OPERATION The heating v...

Page 12: ...t work for air leaks as well as restrictions and blower speed settings If unit performance remains questionable remove charge evacuate to 500 Microns and weigh in refrigerant to name plate charge It i...

Page 13: ...loperateswhenahightemperature condition caused by inadequate airflow occurs This causes the ignition control to close the gas valve The circulation air blower continues to operate in this situation Pr...

Page 14: ...low tipping of the natural gas burner flame or long yellow tips on propane may be caused by lint accumulation or dirt inside the burner or burner ports at the air inlet between the burner and manifold...

Page 15: ...506488 01 Page 15 Issue 1008 Figure 11 Connection Diagram Single Phase PSC Motor...

Page 16: ...N 75 C WIRE WARNING ELECTRIC SHOCK HAZARD UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES HEAT ANTICIPATION SETTING 0 70 AMP LINE VOLTAGE FIELD INSTALLED SEE BLOWER SPEED CHART BLK S...