506488-01

Page 1

Issue 1008

TABLE OF CONTENTS

SAFETY ...............................................................2

INSTALLATION ....................................................2

START-UP .......................................................... 10

OPERATION ...................................................... 11

MAINTENANCE ................................................. 13

CONTROL SYSTEM DIAGNOSTICS .................14

WIRING DIAGRAMS .......................................... 15

Manufactured By

Allied Air Enterprises Inc.

A Lennox International Inc. Company

215 Metropolitan Drive

West Columbia, SC 29170

Do not store combustible materials, including gasoline
and other flammable vapors and liquids, near the furnace,
vent pipe, or warm air ducts. Such actions could cause
property damage, personal injury, or death.

  WARNING

Never use a flame to check for gas leaks.  Explosion
causing injury or death may occur.

  WARNING

If this unit is to be installed in a mobile or manufactured
home application, the ductwork must be sized to achieve
static pressures within the manufacturer’s guidelines.
All other installation guidelines must also be followed.
Failure to do so may result in equipment damage,
personal injury, and improper performance of the unit.

  WARNING

INSTALLATION AND MAINTENANCE INSTRUCTIONS

4PGE/SG(13,15) Series

Gas Heating/Electric Cooling Package Unit

Save these instructions for future reference

The installation of the furnace, wiring, warm air ducts, venting, etc. must conform to the requirements of the National Fire
Protection Association; the National Fuel Gas Code, ANSI Z223.1 (latest edition) and the National Electrical Code, ANSI/
NFPA No. 70 (latest edition) in the United States; the Canadian Installation Codes CAN/CGA-B149.1 & .2 (latest edition)
and the Canadian Electrical Code Part 1, CSA 22.1 (latest edition) in Canada; and any state or provincial laws, local
ordinances, or local gas utility requirements. Local authorities having jurisdiction should be consulted before installation
is made. Such applicable regulations or requirements take precedence over the general instructions in this manual.

 CAUTION

Improper installation, adjustment, alteration, service, or maintenance can cause injury
or property damage. Refer to this manual. For assistance or additional information,
consult a qualified installer, service agency, or the gas supplier.

 

WARNING

*506488-01*

Summary of Contents for 4PGE

Page 1: ...it WARNING INSTALLATION AND MAINTENANCE INSTRUCTIONS 4PGE SG 13 15 Series Gas Heating Electric Cooling Package Unit Save these instructions for future reference The installation of the furnace wiring...

Page 2: ...er charge and airflow may reduce energy efficiency and shorten equipment life Inspection As soon as the unit is received it should be inspected for possible damage during transit If damage is evident...

Page 3: ...pers that will provide continuous heating is not allowed The return air duct must be provided and sealed to the unit Return air temperature must be maintained between 60 F 16 C and 80 F 27 C Air filte...

Page 4: ...above any door window or gravity air inlet into the building The vent system shall terminate at least 3 above any forced air inlet located within 10 The unit shall be installed in a manner such that s...

Page 5: ...nnected to the venting system being placed into operation while all other appliances connected to the common venting system are not in operation 1 Seal any unused openings in the common venting system...

Page 6: ...pening Filters Air filters are to be used with this heating cooling unit Filters are not factory supplied in the unit However a filter frame accessory is available from the manufacturer that allows fi...

Page 7: ...trap drip leg shall be installed as close as practical to the gas supply inlet of the unit LPG Propane Units Tanks and Piping Units are shipped equipped for natural gas but can be converted to LPG pro...

Page 8: ...wiring must be sized to carry minimum circuit ampacity marked on the unit Use copper conductors only Each unit must be wired with a separate branch circuit and be properly fused Thermostat The room t...

Page 9: ...Used WITHOUT ECONOMIZER L2 L1 POWER WIRING 208 230 1 60 75 C MIN WIRE POWER WIRING 24V CONTROL WIRING NEC CLASS 2 GROUND SCREW SINGLE PHASE L1 L2 L3 GROUND SCREW POWER WIRING 200 230 3 60 460 575 3 6...

Page 10: ...hould the supply pressure during standby exceed 13 w c nor should it be less than 5 w c for For Your Safety Read Before Lighting natural gas or 11 W C for propane gas with the burners in operation If...

Page 11: ...contained factory optimized refrigerant system and should require no adjustments when properly installed If however unit performance is questioned perform the following checks OPERATION The heating v...

Page 12: ...t work for air leaks as well as restrictions and blower speed settings If unit performance remains questionable remove charge evacuate to 500 Microns and weigh in refrigerant to name plate charge It i...

Page 13: ...loperateswhenahightemperature condition caused by inadequate airflow occurs This causes the ignition control to close the gas valve The circulation air blower continues to operate in this situation Pr...

Page 14: ...low tipping of the natural gas burner flame or long yellow tips on propane may be caused by lint accumulation or dirt inside the burner or burner ports at the air inlet between the burner and manifold...

Page 15: ...506488 01 Page 15 Issue 1008 Figure 11 Connection Diagram Single Phase PSC Motor...

Page 16: ...N 75 C WIRE WARNING ELECTRIC SHOCK HAZARD UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES HEAT ANTICIPATION SETTING 0 70 AMP LINE VOLTAGE FIELD INSTALLED SEE BLOWER SPEED CHART BLK S...