Electrical Specifications
NOTE: Wire sizes were obtained from the Canadian
Electrical Code for 75 C. wire and are intended for use
as a guideline only. Electrical connections should be
made by a qualified electrical contractor in accordance
with all applicable local and national requirements.
NOTE: Electrical specifications below are subject to
change without notice. Always refer to product serial
plate for most current specifications of product being
installed.
NOTE: Use copper conductors only.
NOTE: Connect to individual branch circuit.
NOTE: 3 Phase Only – Each tumble dryer must be con-
nected to its own individual branch circuit breaker, not
fuses, to avoid the possibility of “single phasing” and
causing premature failure of the motor(s).
050 Series Gas and Steam Models
Serial Plate Rating
Terminal Block
Connections Re-
quired
Serial Plate Amps
Recommended Circuit
Nonre-
versing
Revers-
ing
Breaker
Rating
Wire Size
AWG [mm
2
]
120V/60Hz/1ph
L1, Neutral and ground
9.3
N/A
15A – 1 pole
14 [2.5 ]
120/208-240V/60Hz/1ph
L1, L2, Neutral and ground N/A
12
15A – 1 pole
14 [2.5]
208-240V/60Hz/1ph
L1, L2, Neutral and
ground
5.1
N/A
15A – 1 pole
14 [2.5 ]
200-208-240V/60Hz/1ph
L1, L2 and ground
5.1
N/A
10A – 2 pole
14 [2.5 ]
230-240V/50Hz/1ph
L1, Neutral and ground
6.3
6.9
15A – 1 pole
14 [2.5 ]
200-208/240V/60Hz/3ph
L1, L2, L3 and ground
2.8
4.0
10A – 3 pole
14 [2.5 ]
200V/50Hz/3ph
L1, L2, L3 and ground
3.3
4.2
10A – 3 pole
14 [2.5 ]
230-240V/50Hz/3ph
L1, L2, L3 and ground
3.1
4.3
10A – 3 pole
14 [2.5 ]
380V/50 or 60Hz/3ph
L1, L2, L3 and ground
1.6
2.0
10A – 3 pole
14 [2.5 ]
400-415V/50Hz/3ph
L1, L2, L3 and ground
1.6
2.0
10A – 3 pole
14 [2.5 ]
440V/60Hz/3ph
L1, L2, L3 and ground
1.4
1.9
10A – 3 pole
14 [2.5 ]
460-480V/60Hz/3ph
L1, L2, L3 and ground
1.4
1.9
10A – 3 pole
14 [2.5 ]
N/A = Not Applicable
Table 8
Electrical Requirements
©
Copyright, Alliance Laundry Systems LLC -
DO NOT COPY or TRANSMIT
59
Part No: 70457901ENR15