Chapter 3
Installation and Wiring
3–12
To wire your NR4 module, follow these steps as shown in Figure 3.7:
1. At each end of the cable, strip some casing to expose the individual wires.
2. Trim the signal wires to 5.08–cm (2–inch) lengths. Strip about 4.76 mm
(3/16 inch) of insulation away to expose the end of the wire.
3. At one end of the cable twist the drain wire and foil shield together, bend
them away from the cable, and apply shrink wrap. Then earth ground at
the shield terminal.
4. At the other end of the cable, cut the drain wire and foil shield back to the
cable and apply shrink wrap.
5. Connect the signal wires and cable shield to the NR4 terminal block and
the input.
6. Repeat steps 1 through 5 for each channel on the NR4 module.
Wiring Input Devices to the NR4 Module
Figure 3.7
Shielded Cable
Foil Shield
Drain Wire
(See step 3.)
Signal Wire
Signal Wire
Signal Wire
(See step 4.)
Signal Wire
Signal Wire
Signal Wire
3–Conductor Shielded Cable
Foil Shield
Drain Wire
Signal Wire
Signal Wire
(See step 4.)
2–Conductor Shielded Cable
Signal Wire
Signal Wire
(See step 3.)
AB Spares
Summary of Contents for SLC 500 1746-NR4
Page 1: ...User Manual SLC 500t RTD Resistance Input Module Cat No 1746 NR4 Allen Bradley AB Spares ...
Page 15: ...Preface P 8 Notes AB Spares ...
Page 37: ...Chapter 2 Quick Start 2 12 Notes AB Spares ...
Page 63: ...Chapter 4 Preliminary Operating Considerations 4 12 Notes AB Spares ...
Page 87: ...Chapter 5 Channel Configuration Data and Status 5 24 Notes AB Spares ...
Page 107: ...Chapter 7 Module Diagnostics and Troubleshooting 7 8 Notes AB Spares ...
Page 117: ...Chapter 8 Application Examples 8 10 Notes AB Spares ...
Page 123: ...Appendix A Specifications A 6 Notes AB Spares ...
Page 125: ...Appendix B RTD Standards B 2 Notes AB Spares ...