Chapter 8
Application Examples
8–7
Program Setup and Operation Summary
1. Set up two configuration words in memory for each channel, one for
°
C
and the other for
°
F. Table 8.A shows the configuration word allocation
summary.
Table 8.A
Configuration Word Allocation
annel
Configuration Word Allocation
Channel
°
F
°
C
0
N10:0
N10:4
1
N10:1
N10:5
2
N10:2
N10:6
3
N10:3
N10:7
2. When the position of the degrees selector switch changes, write the
appropriate channel configuration to the RTD module. Note that the use
of the OSR instruction (one–shot rising) makes these configuration
changes edge–triggered, that is, the RTD is reconfigured only when the
selector switch changes position.
°
C
°
F
Degrees Selector Switch
3. Convert the individual RTD data words to BCD and send the data to the
respective LED displays.