Chapter 3
Installation and Wiring
3–8
Figure 3.4
RTD Connections To Terminal Block
2–Wire RTD Interconnection
Chl 1
Shield
Shield
Chl 0
RTD
Shield
RTD
Chl 0
Sense
Chl 1
Sense
Chl 0
Return Chl 1
Return
Shield
Chl 3
Chl 2
RTD
RTD
Chl 2
Sense
Chl 3
Sense
Chl 2
Return
Chl 3
Return
Shield
Shield
Belden #9501 Shielded Cable
RTD
Return
Chl 0 RTD
Chl 0 Sense
Chl 0 Return
Shield
Cable Shield
RTD
Return
Sense
RTD
Sense
Return
3–Wire RTD Interconnection
4–Wire RTD Interconnection
Chl 0 Sense
Chl 0 Return
Shield
Belden #83503 or Belden #9533 Shielded Cable
Cable Shield
RTD
Return
RTD
Sense
Return
Cable Shield
Sense
RTD
Return
Chl 0 RTD
Add Jumper
Chl 0 Sense
Chl 0 Return
Shield
Chl 0 RTD
Belden #83503 or Belden #9533 Shielded Cable
Leave One Sensor Wire Open
Terminal Pin–outs
AB Spares
Summary of Contents for SLC 500 1746-NR4
Page 1: ...User Manual SLC 500t RTD Resistance Input Module Cat No 1746 NR4 Allen Bradley AB Spares ...
Page 15: ...Preface P 8 Notes AB Spares ...
Page 37: ...Chapter 2 Quick Start 2 12 Notes AB Spares ...
Page 63: ...Chapter 4 Preliminary Operating Considerations 4 12 Notes AB Spares ...
Page 87: ...Chapter 5 Channel Configuration Data and Status 5 24 Notes AB Spares ...
Page 107: ...Chapter 7 Module Diagnostics and Troubleshooting 7 8 Notes AB Spares ...
Page 117: ...Chapter 8 Application Examples 8 10 Notes AB Spares ...
Page 123: ...Appendix A Specifications A 6 Notes AB Spares ...
Page 125: ...Appendix B RTD Standards B 2 Notes AB Spares ...