SLC 5/03™, SLC 5/04™, and SLC 5/05™ Modular Processors
9
Publication 1747-IN009C-MU-P - December 2002
2.
Set the communication parameters of the software to match the default parameters of
the processor:
Replacing the Battery
Your SLC processor provides back-up power for RAM through a replaceable lithium battery.
This battery provides back-up for approximately 2 years. The BATT LED on the front of the
processor alerts you when the battery voltage has fallen below a threshold level.
To replace the lithium battery follow these steps:
1.
Remove power from the SLC 500 power supply.
2.
Remove the processor from the chassis by pressing the retainer clips at both the top
and bottom of the module and slide it out.
Channel 0 Configuration Channel 1 Configuration
SLC 5/03, 5/04, 5/05
SLC 5/03
SLC 5/04
SLC 5/05
DF1 Full-Duplex:
•
no handshaking
•
19.2K baud
•
CRC Error Check
•
duplicate detect on
•
no parity
DH-485:
•
19.2K baud
•
node address = 1
DH+™:
•
57.6K baud
•
node address = 1
Ethernet
•
BOOTP
enabled
ATTENTION
!
Do not remove the processor from the SLC 500 chassis until all
power is removed from the SLC 500 power supply
ATTENTION
!
Do not expose the processor to surfaces or other areas that may
typically hold an electrostatic charge. Electrostatic charges can alter or
destroy memory.