12
SLC 5/03™, SLC 5/04™, and SLC 5/05™ Modular Processors
Publication 1747-IN009C-MU-P - December 2002
Communication
Communication options for the SLC 5/03, 5/04, and 5/05 processors are as follows:
•
DH485
•
RS-232 protocols
(DF1 Full-Duplex, DF1 Half-Duplex “master/slave”, DF1 Radio Modem, DH-485,
or ASCII)
•
Data Highway Plus™
(A 1785-KA5P is required for the SLC 5/03 and SLC 5/05 processors.)
•
Ethernet TCP/IP
(A 1761-NET-ENI is required for the SLC 5/03 and SLC 5/04 processors)
•
ControlNet (via a 1747-KFC15)
•
DeviceNet (via a 1761-NET-DNI)
General Specifications
Description
Specification
Power Supply Loading at 5V dc
500 mA for the SLC 5/03 processor
1.0 A for the SLC 5/04 and 5/05 processors
Power Supply Loading at 24V dc
175 mA for the SLC 5/03 processor
0 mA for the SLC 5/04 processor
(1)
(1)
SLC 5/04 Processors manufactured prior to April 2002 draw 200 mA at 24V dc. Check your label to verify your processor’s
current draw.
0 mA for the SLC 5/05 processor
Program Scan Hold-up Time after Loss of
Power
20 ms to 3 s (dependent on power supply loading)
Noise Immunity
NEMA Standard ICS 2-230
Vibration
Displacement: 0.015 inch, peak-to-peak at 5-57 Hz
Acceleration: 2.5Gs at 57-2000 Hz
Shock (operating)
30Gs
Ambient Temperature Rating
Operating: 0 to +60°C (+32°F to +140°F)
Storage: 40°C to +85°C (-40°F to +185°F)
Humidity
5 to 95% without condensation
Agency Certification
UL listed
CSA approved
Class 1, Groups A, B, C or D, Division 2
CE compliant for all applicable directives
C-Tick marked for all applicable acts