Configuring analog output modules
To configure the analog output modules:
Double-click on the IOM with the lowest number after it (for example,
IOM33). This will bring up the window for the 6-channel isolated analog
output module (1756-OF6CI; current output, or 1756-OF6VI; voltage output).
On the IOM Configuration window that is displayed, select the Main tab and
enter the following parameters:
Select the Channel Configuration tab and enter the following parameters for
all channels:
Select the Server Parameters tab and enter the following
(non-case-sensitive) parameters:
Click on OK.
in this field:
enter:
Module Name
LabAO
IOM Slot Number
the slot number containing this module
Remote I/O Chassis Mac Address
0
CNI Slot Number
0
in this field:
enter:
Shed to Safe Value
unchecked (de-select the check mark)
Calibration Bias
0.0
in this field:
enter:
Point Detail Page
sysdtlaoa.dsp
Group Detail Page
sysgrpaoa.dsp