Publication 1734-UM005B-EN-P - June 2001
Default Data Maps
B-11
1734-OE2C Analog Current
Output Module
Product Code: 0019h
Data Map:
Output size: 2 Word; Input size: 0 Word
Configuration Data:
Diagnostic Data
Possible Error Codes:
7
6
5
4
3
2
1
0
Produces (Rx)
Output Channel 0
Output Channel 1
Consumes (Tx)
No consumed data
7
6
5
4
3
2
1
0
Reserved
AD
R
IA
FA
Engineering Units Low (high byte)
Default value = 06h
Engineering Units Low (low byte) Default value = 66h
Engineering Units High (high byte)
Default value = 1Fh
Engineering Units High (low byte) Default value = FFh
Fault Value (high byte)
Default value = 00
Fault Value (low byte)
Default value = 00
Idle Value (high byte)
Default value = 00
Idle Value (low byte)
Default value = 00
Meaning of bits described below
FA = Fault Action
IA = Idle Value
Value
Definition
Value
Definition
0
Hold Last State
0
Hold Last State
1
Fault Value (default)
1
Idle Value (default)
R = Range
AD = Alarm Disable
Value
Definition
Value
Definition
0
4 to 20mA (default)
0
Enable (default)
1
0 to 20mA
1
Disable
Code
Error Type
6
Wire Break
Module incorrect or missing. Reported on channel 0, applies to whole module.
Summary of Contents for POINT I/O PROFIBUS 1734-APB
Page 1: ...POINT I O PROFIBUS Adapter Module Cat No 1734 APB User Manual Allen Bradley HMIs...
Page 6: ...Publication 1734 UM005B EN P June 2001 Preface 4...
Page 24: ...Publication 1734 UM005B EN P June 2001 2 10 Installing the PROFIBUS Adapter...
Page 62: ...Publication 1734 UM005B EN P June 2001 6 4 Troubleshooting the PROFIBUS Adapter...
Page 82: ...Publication 1734 UM005B EN P June 2001 B 18 Default Data Maps...
Page 84: ...Publication 1734 UM005B EN P June 2001 2...
Page 87: ...Allen Bradley HMIs...