Chapter
5
Grouped Mode
In This Chapter
In this chapter, you will learn about:
General
In order to use master memory most effectively, and reduce data
transfer between the POINT I/O adapter and the master, you can
group several modules in a single byte.
To configure the adapter for grouped mode you must:
1.
insert modules adjacent to each other
2.
Modules must be in the same module family
Groups may exist as follows:
•
1734-IB2, 1734-IV2, 1734-IM2 and 1734-IA2 can be grouped
together
•
1734-IB4 and 1734-IV4 can be grouped together
•
1734-OW2, 1734-OA2 and 1734-OX2 can be grouped together
The following modules
cannot
be grouped with any other
module type:
•
1734-OB2E can only be grouped with 1734-OB2E modules
•
1734-OB4E can only be grouped with 1734-OB4E modules
3.
A maximum of 8 channels (1 byte) per group
4.
Modules in a single byte will have the configuration of the first
module in the group. (Exception: Extended diagnostics can be
enabled/disabled on a per module basis.)
For more information about:
See page:
How to Configure the Adapter for Grouped Mode
Summary of Contents for POINT I/O PROFIBUS 1734-APB
Page 1: ...POINT I O PROFIBUS Adapter Module Cat No 1734 APB User Manual Allen Bradley HMIs...
Page 6: ...Publication 1734 UM005B EN P June 2001 Preface 4...
Page 24: ...Publication 1734 UM005B EN P June 2001 2 10 Installing the PROFIBUS Adapter...
Page 62: ...Publication 1734 UM005B EN P June 2001 6 4 Troubleshooting the PROFIBUS Adapter...
Page 82: ...Publication 1734 UM005B EN P June 2001 B 18 Default Data Maps...
Page 84: ...Publication 1734 UM005B EN P June 2001 2...
Page 87: ...Allen Bradley HMIs...