Installing the PROFIBUS Adapter
2-9
PROFIBUS Connection Plug Wiring
Chapter Summary and
What’s Next
In this chapter, you learned how to install and wire your adapter.
Move to chapter 3 for information on configuring the POINT I/O
system.
Pin Number
Name
Description
Housing
Shield
Connected to Chassis Ground
1
Not connected
2
Not connected
3
RX/TX Data +
Positive RX/TX data line
4
RTS
Request to send
5
Data Ground
Isolated ground
6
+5V BUS
Is5V from RS485 side
7
Not connected
8
RX/TX Data -
Negative RX/TX data line
9
Not connected
PROFIBUS connection
Pin 3 - RX/TX Data +
Pin 8 - RX/TX Data
-
Pin 6 - +5V
Pin 4 - Request to send (RT
Pin 5 - Data Ground