
POINT I/O 2 Current Output and 2 Voltage Output Analog Modules
5
Publication 1734-IN002E-EN-E - October 2016
European Hazardous Location Approval
The following applies when the product bears the Ex Marking
This equipment is intended for use in potentially explosive atmospheres as defined by
European Union Directive 2014/34/EU.
DEMKO certifies that this equipment has been found to comply with the Essential Health
and Safety Requirements relating to the design and construction of Category 3 equipment
intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this
Directive.
Compliance with the Essential Health and Safety Requirements has been assured by
compliance with EN 60079-0:2012+A11:2013, EN 60079-15:2010, reference certificate
number DEMKO 04ATEX0330347X.
ATTENTION:
This equipment is not resistant to sunlight or other sources of
UV radiation.
WARNING:
This equipment shall be mounted in an ATEX certified enclosure
with a minimum ingress protection rating of at least IP54 (as defined in
IEC/EN 60529) and used in an environment of not more than Pollution Degree
2 (as defined in IEC/EN 60664-1) when applied in Zone 2 environments. The
enclosure must utilize a tool removable cover or door.
WARNING:
This equipment shall be used within its specified ratings defined
by Rockwell Automation.
WARNING:
Provision shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 140% of the rated voltage
when applied in Zone 2 environments.
WARNING:
The secondary of a current transformer shall not be
open-circuited when applied in Class I, Zone 2 environments.
WARNING:
This equipment must be used only with ATEX certified Rockwell
Automation backplanes
WARNING:
Secure any external connections that mate to this equipment by
using screws, sliding latches, threaded connectors, or other means provided
with this product.
WARNING:
Do not disconnect equipment unless power has been removed or
the area is known to be nonhazardous.