18
POINT I/O 2 Current Output and 2 Voltage Output Analog Modules
Publication 1734-IN002E-EN-E - October 2016
Placing Series C Analog Current Output Modules
Always install modules in accordance with their specified operating temperature ratings, as
listed in Environmental Specifications on page 20, and provide a minimum of
2.54 cm (1.0 in.) clearance above the modules.
Specifications
Flashing Green
Channel is being calibrated.
Flashing Red
Open wire or no field power is present.
A low or high clamp is present.
Red
—
No field power is present.
Output Specifications
Output Specifications
1734-OE2C
1734-OE2V
Number of Outputs
2 single-ended, non-isolated,
current
2 single-ended, non-isolated,
voltage
Resolution
13 bits - over 0-21mA
2.5
μ
A/cnt (average value -
typical range:
2.3...2.7
μ
A/cnt)
14 bits
(13 plus sign)
1.28mV/cnt in unipolar or bipolar
mode
Output Current
0 mA output until
communication established
4...20 mA user configurable
0...20 mA user configurable
—
Output Voltage
—
0V output until communication
established
0...10V (user configurable)
(-0.0V under, +0.5V over)
+10V user configurable (-0.5V under,
+0.5V over)
Absolute Accuracy
(1)
0.1% full scale @ 25
o
C
Accuracy Drift w/Temp.
30ppm/
o
C
5ppm/
o
C
Step Response to 63% of FS
24
μ
s
Channel Status
Indication
Probable Cause
1734-OE2C
Probable Cause
1734-OE2V