Allen-Bradley MSR42 User Manual Download Page 8

6   

Light Curtain Multi-Function Control Module User Manual

Or

i

g

i

nal 

i

nstruct

i

ons

Earth connect

i

on

The earth of each MSR42 control module is realized through the 
connection to the mounting rail. Consequently it is important to ensure, 
that the mounting rail has a good earth connection.

M

i

cro400 l

i

ght curta

i

n

The two RJ45 sockets on the lower portion of the control module are for 
the connection of Allen-Bradley GuardShield Micro400 (white = E = 
emitter; blue = R = receiver). To help protect the RJ45 connectors the 
cables have to be snapped into the provided cable holders at the.MSR42 
housing.

Start 

m

ode

The MSR42 can be configured to have the following start modes:

• automatic start or
• manual start.

In case of the basic configuration the start mode can also be configured 
without the configuration software.  By conn24V to GPI03 and 
GPI04, automatic reset is enabled (see wiring diagrams).

Manual start

When all of the inputs of the safety system have a safe signal, depressing 
the start button will cause the two safety OSSD outputs to change from 
low to high.  If a MSR45E relay expander module is connected, it will 
close. If more than one safety component is configured, then all 
components must have safe signals to all inputs before a start is allowed. 
The start button is monitored to prevent an unintentional start.  Pulse 
length must be between: 50 ms and 5 sec. If the start impulse is longer or 
shorter, the start input will be ignored by the device.  The configuration 
control document identifies which terminal the start button is connected 
to.  If the start button is connected to IN1or IN2 then a red LED 
indicates that a start signal is present, a green LED indicates no signal is 
present.

Table 4

Warning: Important safety advice:

Automatic start

If a safety component is configured for “automatic start”, then, after the 
activation and the deactivation of the safety component, the two OSSD 
outputs will change automatically from low to high again and if 
connected the MSR45E expander relay contacts will automatically re-
close.

M

i

n

im

u

m

 o

ff

 t

im

e

According to the standard IEC 61496-2 a safety light curtain must have a 
minimum safety output off time of 80 ms. This means that even in the 
case of a very short safety light curtain interruption, the safety outputs 
will stay low (Relays = open) for 80ms at minimum. A start signal will 
only be recognized after the 80ms duration.

EDM or start release

If an MSR42 is used with external relays or contactors, the contacts of 
that device must be monitored. An example category 4 application has 
two external contactors, each with force guided contacts must be 
inserted. For monitoring the function of these contactors, each relay 
block must have at least one normally closed contact which is fed back in 
series to IN2 (or IN1 depending on configuration) of the MSR42 
control module (e.g. Figure 4).

Two options are possible for this monitoring:

1. Start release: The signal at the corresponding input terminal must be 
high before the start button is pressed (this means: the normally closed 
contacts of the external relays must be closed before allowing a start). The 
option “start release” is pre-configured in the MSR42 control module 
(440R-P226AGS-NNR) (e.g. Figure 4).

2. EDM (external device monitoring): The input signal of the EDM 
terminal is always monitored. This means: not only at the beginning 
before a start the signal must be correct. Also after the start a signal 
change must happen, otherwise an emergency stop occurs. If a high signal 
is present for longer than 5 seconds, a lock-out will occur. 

If the configuration control document shows that EDM or start release 
must be attached to terminal IN 1 or IN 2, then the meaning of the 
respective LED is shown below.

Table 5

The start release or EDM input is not cross-fault monitored and 
therefore not a safety input.

Terminal

LED green

LED red

IN 1 or IN 2

No start signal present

Start signal present (button pressed)

It is fundamental that the start button be 
mounted so that the danger area is clearly 
visible. That is, when pressing the start 
button it must be guaranteed that no one 
is detained within the danger area.

According to EN 60204 article 9.2.4.4.2 a 
system may not automatically restart, 
even after the cause of the shutdown has 
been eliminated and thereby another 
danger may still exist to the operator. If 
the MSR42 control module is configured 
with an “automatic start”, this 
requirement must be fulfilled by further 
measures.

Terminal

LED green

LED red

EDM at IN 1 or IN 2

EDM signal okay

EDM signal wrong

Start release at IN 1 or 

IN 2

Start release signal okay

Start release signal wrong

Summary of Contents for MSR42

Page 1: ...MSR42 Control Module User Manual...

Page 2: ...GI 1 1 Safety Guidelines for the Application Installation and Maintenance of Solid State Control available from your local Rockwell Automation sales office describes some important differences between...

Page 3: ...nd GmbH are available online at www ab com The actual list of relevant safety data and applied standards is given in these documents Introduction The MSR4x is a family of extremely compact safety cont...

Page 4: ...light curtain Figure 16 Applications Typical applications Typical MSR42 base module applications are Presses Robotic cells with automatic insertion Assembly lines Indexing tables Conveyor systems Auto...

Page 5: ...ustomer Configurations The configuration of a MSR42 control module is set up via of the USB optical interface and the Allen Bradley GuardShield Software Configuration Diagnostic Tool The configuration...

Page 6: ...and c All relevant data of the actual configuration are always described in the actual configuration control document for that controller Make sure that the actual document is always stored near to t...

Page 7: ...SD t em Basic configuration The maximum controller response time t C for the MSR42 control module is given in chapter 14 However depending from the connected Micro 400 light curtain the response time...

Page 8: ...e of a very short safety light curtain interruption the safety outputs will stay low Relays open for 80ms at minimum A start signal will only be recognized after the 80ms duration EDM or start release...

Page 9: ...if e g the protective field is interrupted Figure9 ConnectingaSafetyOverridekeyswitchandtheassociatedlamp Depending on the risk evaluation when using a Safety override key operated switch a correspond...

Page 10: ...wo types of blanking available through the MSR42 Fixed blanking Floating blanking When blanking is activated this has to be clearly indicated by a display or a lamp The MSR42 has only one monitored ou...

Page 11: ...he double scan mode in the Micro 400 window of the MSR42 Configuration Diagnostic Tool software see Double Scan Filter in Software Configuration Tool Manual Testing the MSR42 standard Blanking area Fi...

Page 12: ...aults apply to the Out of Box configurations only Reference Table 15 for detailed information Table15 The lock out mode of a MSR42 control module may be reset by one of two methods 1 Power down then P...

Page 13: ...40R P226AGS NNR Relay Input Voltage Reset Outputs Cat No MSR45E Safety Relay Expansion Module SuppliedbyMSR41 or MSR42 Determined by MSR41 or MSR42 2 N O 440 P4NANS Part number Description 440R ACABL1...

Page 14: ...y HW Hardware Version SafetyLevel Cat Safetycategory according to EN ISO 13849 1 SafetyLevel SIL Safety integrity level according to EN 61508 SafetyLevel PL Performance level acc to EN ISO 13849 1 Pow...

Page 15: ...t UN coded Maximum cable length for safety switches 50 m out and back total 100 m See page 6 or 10 Safety Prevention Lamp Minimum current at Lamp 0 9 A with lamp switched on GPIO1 GPIO4 Outputs to saf...

Page 16: ...ro 400 Evaluation time t EvalLC see label light curtain only important for interrupt ignore time Controller response time t C 14 70 ms Stop delay time t delay 0 00 ms Interrupt ignore time t ignore 0...

Page 17: ...2004 A1 2008 Safety of machinery Electro sensitive protective equipment Part 1 General requirements and tests IEC 61496 2 2006 Safety of machinery Electro sensitive protective equipment Part 2 Particu...

Page 18: ...221AGS MSR41 base module 440R P226AGS NNR MSR42 base module 445L 104794 B MSR42 base module customer configuration 440R P4NANS MSR45E expander module 445L 1 MSR45E expander module customer configurati...

Page 19: ...hi toimuda enne kui installeerija on omandanud koopia tootja instruktsioonidega keeles mida ta ise valdab Instruktsioonid erinvates keeltes on saadaval siin http rockwellautomation com literature SUOM...

Page 20: ...aan Boulevard du Souverain 36 1170 Brussels Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax...

Reviews: