Assembly and Installation
Chapter 3
34
Figure 3.3
Typical Suppression for Large AC Inductive Load
10111I
0.47
220
W
m
f
Electrocube
Part No. RG167614
V130 LA1
Discrete Component Equivalent
General Electric MOV (Metal Oxide Varistor)
120V AC
CR4
Figure 3.4
Typical Suppression for Small DC Inductive Load
10112-I
+
V DC
-
PIV (Peak Inverse Voltage) rating of diode
must be at least twice the applied DC voltage
All possible sources of noise should be suppressed. Best results are achieved
when the noise-suppressing networks are connected as closely as possible to the
“noisy” device.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com