6–7
Input, Output and Configuration Files for Analog Modules when used with ControlNet
Publication 1794-6.5.16 – September 1998
Definition
Bit
Input
Word
7
Bits 00–15
(00–17)
Counter 31 – pulse counter or high word of 32-bit period measurement for channel 3
Word 8
Bit 00
Positive edge – Channel 0 – measurement ready
Bit 01
Positive edge – Channel 1 – measurement ready
Bit 02
Positive edge – Channel 2 – measurement ready
Bit 03
Positive edge – Channel 3 – measurement ready
Bit 04–15
Reserved for factory use
Word 9
Bits 00–15
(00–17)
Software revision – version code of software installed
Configuration
Word
Bit
Definition
Configuration
Wor 0
Control Word 0 – Control word for setting the function of counter 0.
Word 0
Bits 00
Pulse counting and period time measurement selection for Channel 0 –
0 = pulse counting and period time measurement selected
1 = period time measurement selected
Bits 01
Pulse counting and period time measurement selection for Channel 1 –
0 = pulse counting and period time measurement selected
1 = period time measurement selected
Bits 02
Pulse counting and period time measurement selection for Channel 2 –
0 = pulse counting and period time measurement selected
1 = period time measurement selected
Bits 03
Pulse counting and period time measurement selection for Channel 3 –
0 = pulse counting and period time measurement selected
1 = period time measurement selected
Bits 04–15
(04–17)
Reserved