4–4
Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter
Publication 1794-6.5.16 – September 1998
Definition
Bit
Read
Word
Word 8
Bit 00
Positive edge – Channel 0 – measurement ready
Bit 01
Positive edge – Channel 1 – measurement ready
Bit 02
Positive edge – Channel 2 – measurement ready
Bit 03
Positive edge – Channel 3 – measurement ready
Bit 04–15
Reserved for factory use
Word 9
Bits 00–15
(00–17)
Software revision – version code of software installed
Block Transfer Write Word Assignments for the Pulse Counter
Module
(Octal Bit)
⇒
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Dec. Bit
⇒
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Word
⇓
Write
0
Control Word 0 – selects the measure function
1
Control Word 1 – sets the clock frequency and period multiple
2
Control Word 2 – sets the start of a new measurement
3–4
Not used
Bit/Word Definitions for the Block Transfer Write Words for the Pulse
Counter Module
Write
Word
Bit
Definition
Write
Wor 0
Control Word 0 – Control word for setting the function of counter 0.
Word 0
Bits 00
Pulse counting and period time measurement selection for Channel 0 –
0 = pulse counting and period time measurement selected
1 = period time measurement selected
Bits 01
Pulse counting and period time measurement selection for Channel 1 –
0 = pulse counting and period time measurement selected
1 = period time measurement selected
Bits 02
Pulse counting and period time measurement selection for Channel 2 –
0 = pulse counting and period time measurement selected
1 = period time measurement selected
Bits 03
Pulse counting and period time measurement selection for Channel 3 –
0 = pulse counting and period time measurement selected
1 = period time measurement selected
Bits 04–15
(04–17)
Reserved